Get a quote

Street Light Installation Procedure: From Setting Out to Switch-On

The installation procedure for grid-powered LED street lights on a road: setting out, cable sizing with a voltage-drop example, poles, arms, wiring, testing and commissioning, with a real project.

Key points

  • A road lighting job runs in a fixed order: design and setting out, ducts and foundations, cables, poles and arms, luminaires, testing, commissioning and records.
  • In our calculator, a 7 m road with 10 m poles and 100 W LDM30C heads needs a pole every 35 m on one side for class M3, about 29 poles per km.
  • Voltage drop decides the cable: fifteen 100 W lights on one 230 V feeder drop about 4.3 V (1.9 %) on 16 mm² copper, but about 11.6 V (5 %) on 6 mm².
  • Our steelworks road project in Xiangtan installed 43 poles, 47 floodlights, 5 control boxes and more than 1,600 m of cable in one month.

A street lighting project looks simple from the roadside: poles go up, lights come on. On site it is a sequence of trades — surveyors, civil crews, cable jointers, crane operators and electricians — and each one depends on the step before. This guide sets out a practical installation procedure for grid-powered LED street lights on a public or private road. For solar street lights, which skip the cabling but add batteries and panels, see how to install a solar street light.

Phase 1: Design and setting out

Fix the design numbers

The installation crew needs four numbers per road: pole height, luminaire wattage, spacing and arrangement (one side, staggered or opposite). They come from the lighting class of the road. Our EN 13201 road lighting classes guide explains how to pick the class. If the job replaces old sodium lanterns on existing poles, replacing high pressure sodium lights with LED covers the retrofit version of this procedure.

A worked example for a 7 m two-lane road, class M3 (average 15 lux), with 10 m poles and our LDM30C modular street light at 100 W and a conservative 110 lm/W. Our pole height and spacing calculator gives (open the example):

  • single-sided arrangement, because the road is narrower than the pole height;
  • 35 m spacing, about 15.5 lux average;
  • 29 poles per km, 2.9 kW per km.

The spacing is held at 3.5 times the pole height for uniformity, which is why the 100 W head meets the class with almost no margin. The calculator shows that about 97 W would be enough at that spacing. For a deeper look at spacing, see street light pole distance calculation.

Set out on site

Mark every pole position with pegs and paint. Then walk the line and check each mark against:

  • underground services (water, gas, telecom), using utility drawings and a cable locator;
  • driveways, junctions and pedestrian crossings, where a pole may need to move a few metres;
  • trees, which will grow into the light distribution;
  • overhead lines and the clearance required by the power company.

Small moves are fine; large moves change the uniformity, so re-run the calculation if a pole moves more than about 10 % of the spacing.

Phase 2: Civil works

Ducts and trenches

Cables are usually pulled through ducts, not laid directly. Ducts cross under the road at the planned positions, with draw pits or hand holes at changes of direction. Keep the trench open for as short a time as possible on a live road and plan traffic management with the road authority.

Foundations

Each pole sits on a concrete foundation with anchor bolts, or is set directly in the ground for some small poles. The size depends on pole height, arm length, luminaire area and wind speed. Our street light foundation design guide works through an 8 m example. Concrete needs time to cure before the pole is loaded: follow the mix design, typically about a week before full load.

Phase 3: Cables and electrical design

Sizing the feeder for voltage drop

Long street lighting circuits are limited by voltage drop rather than current. Take the example road: fifteen 100 W lights at 35 m spacing on one single-phase 230 V feeder, so the last light is 525 m from the supply. Each light draws about 100 ÷ (230 × 0.97) ≈ 0.45 A.

With the loads spread evenly, the drop is 2 × R × I × spacing × n(n+1)/2, where R is the cable resistance per metre and n is the number of lights:

Cable (copper) Resistance Voltage drop at last pole % of 230 V
6 mm² 3.08 Ω/km ≈ 11.6 V ≈ 5.0 %
10 mm² 1.83 Ω/km ≈ 6.9 V ≈ 3.0 %
16 mm² 1.15 Ω/km ≈ 4.3 V ≈ 1.9 %

The LDM30C driver accepts AC 185–264 V, so all three would light. But many codes limit voltage drop to 3–5 %, and a three-phase feeder with lights shared across phases reduces the drop further. Size the cable to your code, not just to what the driver tolerates.

Earthing and protection

Each circuit needs overcurrent protection and, under most codes, residual current protection. Metal poles are bonded to the protective conductor, and many utilities add an earth electrode at the feeder pillar and at the end of each run. IEC 60364-7-714 covers external lighting installations.

Phase 4: Poles, arms and luminaires

  1. Assemble on the ground. Fit the arm and, where practical, the luminaire and the internal cable before lifting. Our street light bracket guide covers arm types.
  2. Lift and set. Use a crane or truck-mounted lifter, stand the pole on the anchor bolts, and level it with the levelling nuts.
  3. Plumb and tighten. Check vertical in two directions, tighten the nuts to the specified torque, then fill under the base plate if the design requires grout.
  4. Set the tilt and orientation. Aim the luminaire square to the road and set the tilt from the design, usually 0–10°.
  5. Wire inside the pole. Terminate the supply cable on the fuse or terminal block at the hand hole, run the cable to the luminaire, and close the door. See light pole hand holes for the details.

Phase 5: Controls

Most new LED roads use one of three control methods:

Set the dimming profile at this stage; it is easier than revisiting every light later.

Phase 6: Testing and commissioning

Before switching on:

  • insulation resistance of each circuit, conductor to conductor and to earth;
  • continuity of the protective conductor to every pole;
  • earth electrode resistance;
  • polarity at every luminaire.

After switching on:

  • walk or drive the road at night and confirm every light works and none is aimed wrongly;
  • measure illuminance at a few points and compare with the design;
  • confirm the photocell, timer or dimming profile behaves as set.

From our own projects

On the steelworks road lighting upgrade in Xiangtan, the job covered 43 new LED street light poles, 47 LED floodlights, 5 lighting control boxes and more than 1,600 m of cable for dark road sections inside a working steel plant, supplied and installed in one month. The tight schedule worked because the sequence above was planned around plant traffic, with trenching and pole setting done in short sections.

Handover records

Give the owner an as-built drawing with pole numbers, cable routes and circuit numbers, the test results, the luminaire model and wattage per pole, and the control settings. These records make the first fault call much faster.

What to send us

Road widths, lengths, pole height preferences, lighting class or target lux, and supply voltage. We will reply with spacing from our calculator, a luminaire selection and a cable schedule outline.

Sources

  1. EN 13201-2 — Road lighting, Part 2: Performance requirements
  2. IEC 60364-7-714 — Low-voltage electrical installations: External lighting installations
  3. CIE 115 — Lighting of roads for motor and pedestrian traffic
  4. BlueGreen OE — LDM30C modular LED street light

Frequently asked questions

What is the first step in a street light installation?

The lighting design and setting out: choose the lighting class, pole height, wattage and spacing, then mark each pole position on site and check it against underground services, driveways and trees.

How deep should street light cables be buried?

It depends on the local code. Many codes ask for cables in ducts at roughly 0.6–0.8 m under verges and deeper under carriageways, with warning tape above. Follow your utility's standard drawing.

How do you test a new street lighting circuit?

Before energising: insulation resistance between conductors and to earth, continuity of the protective conductor, earth resistance at the pole or feeder pillar, and polarity. After energising: check every light, the controls and the illuminance on the road.

How many street lights can one circuit feed?

As many as the cable and protection allow while keeping voltage drop within the limit, often 3–5 %. In our example, fifteen 100 W LED lights on a 525 m run of 16 mm² copper drop only about 1.9 %.

What tilt should a street light head have?

Usually 0–10°, set from the photometric design. Our LDM30C has an adjustable angle; tilting more than needed raises glare and wastes light behind the pole.

Products in this guide

Have a project?

Ask our engineers

Send us your site details and we will size the system and quote it.

We reply by email within one working day (China time, GMT+8). Your details are only used to answer this inquiry. Prefer chat? Message us on WhatsApp. Have more detail to give? Use the full form.

Related guides