High Bay Lighting Design: A Step-by-Step Method with a Worked 60 × 30 m Hall

High bay lighting design in seven steps: brief, light level, mounting height, fitting and beam, count, spacing check and controls, worked through for a 60 × 30 m hall at 10 m.

Key points

  • A high bay design is a sequence: brief, target illuminance, mounting height, fitting and beam, count by the lumen method, spacing and uniformity check, then controls and emergency lighting.
  • For a 60 × 30 m hall at 10 m and 300 lux, our calculator gives 45 fittings of 200 W at 130 lm/W, about 350 lux and 5 W/m²; 150 W fittings need 60, 240 W need 40, all at a similar W/m².
  • Spacing, not only lumens, sets the count: keep fittings no more than about 1.2 times the mounting height apart for a medium beam, 1.5 for wide and 0.9 for narrow.
  • We supplied 600 of our 150 W high bays for 13 m production halls at Hunan Nantong Group, accepted in November 2024.

A high bay lighting design does not start with a fitting. It starts with the hall and the work done in it. Get the brief right and the rest becomes arithmetic; get it wrong and a perfectly good fitting ends up in the wrong place. This guide sets out the seven steps we follow, and works them through for a 60 × 30 m hall with a 10 m mounting height.

Step 1: the brief

Collect these before calculating anything:

  • Hall length, width and mounting height (to the bottom of the fitting, not the roof apex)
  • What happens on the floor: storage, assembly, inspection, loading
  • Racking layout and height, if any; crane runways and their clearance
  • Surface colours (roof, walls, floor) or at least light / medium / dark
  • Ambient temperature, dust, humidity, wash-down
  • Supply voltage, switching and any sensor or daylight requirements
  • Daylight from roof lights or windows

Our warehouse lighting design quote guide lists twelve facts to send a supplier; it is the same list.

Step 2: the target light level

Choose the maintained illuminance by task, and zone the hall if tasks differ. Typical values from EN 12464-1:

Area Maintained illuminance
Bulk storage, rarely visited 100–150 lux
Packing, dispatch, loading bays 200–300 lux
General assembly, machining 300 lux
Fine assembly, inspection 500–750 lux

Our warehouse lighting lux levels guide gives more detail. For the worked hall we take 300 lux for general assembly.

Step 3: the mounting height

The calculation uses the height of the fitting above the working plane, Hm. With fittings at 10 m and a working plane at 0.8 m, Hm = 9.2 m. This also sets the maximum spacing (step 6) and the beam choice (step 4).

Step 4: the fitting and the beam

Match the fitting to the environment first, then the optics to the geometry:

Condition Suitable type
Dry, clean, 4–8 m Lightweight fin high bay such as the GKP40J, 60–250 W
Dusty, humid or 6–12 m IP65 heat-pipe high bay such as the GKP40G, 60–250 W, >130 lm/W
Above 12 m, or high power per point High-power heat-pipe high bay
Hot ceilings, foundries High-temperature high bay rated for the ambient

For beams, a rule of thumb: 120° below about 6 m, 90° at 6–10 m, 60° above 10 m or in rack aisles. Our UFO vs linear high bay guide covers the shape question.

Step 5: the count, by the lumen method

The lumen method gives the number of fittings:

N = E × A ÷ (Φ × UF × MF)

where E is the target illuminance, A the floor area, Φ the lumens per fitting, UF the utilisation factor (from the room index and reflectances) and MF the maintenance factor. Our high bay and warehouse lighting calculator does this and then rounds up to a regular grid.

For the 60 × 30 m hall, 300 lux, medium reflectances, MF 0.8 and GKP40G fittings at 130 lm/W:

Fitting power Fittings (grid) Spacing Average illuminance W/m²
150 W 60 (10 × 6) 6.0 × 5.0 m about 350 lux 5.0
200 W 45 (9 × 5) 6.7 × 6.0 m about 350 lux 5.0
240 W 40 (8 × 5) 7.5 × 6.0 m about 374 lux 5.3

(Open the 200 W example.)

All three land at a similar load per square metre: the energy depends on efficacy and the target, not on how the lumens are packaged. The choice between them is about uniformity, cost per point, and how many points the cabling and the crane clearances allow. More, smaller fittings give better uniformity and soften shadows; fewer, larger ones save installation labour.

Step 6: check spacing and uniformity

The lumen method gives an average. It does not prevent dark bands between rows if the fittings are too far apart. Check the spacing against the beam:

Beam Maximum spacing At Hm = 9.2 m
Wide 1.5 × Hm 13.8 m
Medium 1.2 × Hm 11.0 m
Narrow 0.9 × Hm 8.3 m

All three layouts in the table are well inside the medium-beam limit, so uniformity should be comfortable. In a racked warehouse the rule changes: fittings go over the aisles, one row per aisle, and the spacing along the aisle is checked against the beam’s long axis. A point-by-point calculation in lighting software confirms the minimum before the order.

Step 7: controls, emergency and maintenance

  • Controls. Occupancy sensors in low-traffic zones and daylight dimming under roof lights often save more energy than any fitting choice. See high bay occupancy sensors.
  • Emergency lighting. Escape routes and high-risk task areas need emergency lighting to the local code.
  • Access. At 10 m and above, plan how fittings will be reached: lift, platform, or crane walkway. Heavier fittings need rated hooks or brackets.

A real installation at 13 m

For Hunan Nantong Group we supplied 600 of our 150 W LED high bays for production halls with fittings at 13 m; the project was accepted in November 2024. In April 2026 our team returned to service and replace fittings in one hall from an aerial platform at 9 m. A new hall for Zhuzhou Linghang Automation was fitted with our 250 W high bays and accepted in June 2025. The details are on the factory high bay project page.

Common mistakes

  • Using the roof apex as the mounting height. It inflates the room index and under-counts fittings.
  • One light level for the whole hall. Storage zones lit to assembly levels waste energy for years.
  • Skipping the spacing check. A good average with dark aisles is still a failed design.
  • Ignoring the environment. An IP20 fitting in a dusty plant loses output within months; choose IP65 where dust or humidity is present.

To check a design after installation, measure it on a proper grid as described in our foot-candle measurement guide, and compare with the calculation for the same layout.

Sources

  1. EN 12464-1:2021 — Lighting of indoor work places
  2. IES — Recommended practice for industrial facilities
  3. BlueGreen OE — LED high bay lighting for factories (project)
  4. BlueGreen OE — High bay and warehouse lighting calculator

Frequently asked questions

What is high bay lighting design?

Choosing the fittings, their number and their positions for a hall with a mounting height of roughly 6 m or more, so that the floor or task plane gets the required illuminance and uniformity with acceptable glare and energy use.

How far apart should high bay lights be?

No more than about 1.2 times the mounting height above the working plane for a medium beam, 1.5 times for a wide beam and 0.9 times for a narrow beam. At 10 m with a 0.8 m working plane, that is about 11 m for a medium beam.

What lux level should a warehouse or factory have?

Typical values from EN 12464-1 are 100–150 lux for storage areas, 200 lux for packing and dispatch, 300 lux for general assembly and 500 lux or more for fine work. The design should follow the task in each zone.

Is a narrow or a wide beam better for high bays?

Narrow beams suit high mounting and rack aisles; wide beams suit lower ceilings and open floors. Narrow beams put more light on the floor but need closer spacing; wide beams allow wider spacing but lose more light to walls.