High bay lighting calculator

How many LED high bays does your warehouse, factory or sports hall need? Enter the hall size, mounting height and target light level to get the number of fixtures, a layout grid, the spacing check and the power density.

Building
Target
Luminaire

Result

How this was calculated

    Get a quote for this design

    Method

    The calculator uses the lumen method from lighting design practice: N = E × A ÷ (Φ × UF × MF). The utilisation factor (UF) depends on the room index K = L × W ÷ (Hm × (L + W)), where Hm is the height of the luminaire above the working plane, on the beam angle and on how much light the ceiling, walls and floor reflect.

    The number is then arranged in a grid, and the grid is checked against the maximum spacing for the beam angle, so the light is even and not just high on average. When spacing forces more fixtures than the light level needs, the calculator suggests a lower wattage per fixture.

    Worked example

    A 60 × 30 m warehouse, 10 m mounting height, 200 lx, 150 W high bays at 130 lm/W with 90° beams: Hm = 9.2 m, K ≈ 2.2, UF ≈ 0.67. N = 200 × 1,800 ÷ (19,500 × 0.67 × 0.8) ≈ 35. Arranged to the hall’s proportions this becomes an 8 × 5 grid of 40 fixtures at 7.5 × 6 m, well inside the 11 m spacing limit (1.2 × 9.2 m), for about 230 lx average.

    Free to use on your website

    Embed this calculator

    Writing about street lighting or solar? Paste this code into your article or page and your readers can use the calculator without leaving your site. It is free, has no ads and needs no sign-up. Please keep the credit line under the frame.

    Works in WordPress (Custom HTML block), Webflow, Wix, Squarespace and plain HTML.

    Preview

    Questions about this calculation

    How many lux does a warehouse need?

    EN 12464-1 recommends about 100 lx for storage areas, 150 lx where people pick goods, 200 lx for loading bays and rough work, 300 lx for workshops and assembly, and 500 lx for fine assembly and inspection. Local codes and client standards may require more.

    How far apart should high bay lights be?

    Spacing should not exceed about 1.5 × the mounting height for wide 120° beams, 1.2 × for 90° and 0.9 × for 60° narrow beams. Wider spacing leaves dark patches between fixtures even when the average lux is high.

    Which beam angle should I choose?

    Use 90°–120° in open halls with mounting heights up to about 10 m, 60°–90° for 10–15 m, and narrow beams (30°–60°) for very high ceilings and racking aisles, where the light must reach the floor between tall racks.

    What is the maintenance factor?

    It accounts for light lost over time from LED depreciation and dirt on the luminaire. 0.8 is typical for LED high bays in clean halls; use 0.7 in dusty plants such as foundries and cement works.

    Next step

    Ask our engineers to check your design

    Calculators give planning figures. Send us the site location, drawings and quantity, and we return a photometric or solar sizing check and a quotation for the complete set.

    Email us