How to Get a Custom Lighting Design Quote for a Large Warehouse (and What It Should Contain)

How to get comparable lighting design quotes for a large warehouse: the 12 facts to send, what a quote should contain, and a worked 120 × 80 m example.

Key points

  • Suppliers can only quote comparably if they all receive the same brief: dimensions, mounting height, racking layout and target lux.
  • A real design quote contains a layout drawing, a fitting schedule, calculated lux and uniformity, the connected load and the assumptions used.
  • For a 120 × 80 m warehouse at 12 m, 200 lux needs about 165 fittings of 200 W; 150 lux needs 117 and 300 lux needs 247.
  • Beam angle and wall colour each move the count by 7–9% in the same building, so check that every quote uses the same assumptions.
  • The calculator count is for open floor. Racked aisles need aisle optics and a row above every aisle.

Ask three suppliers to quote lighting for the same warehouse and you will often get three different numbers of fittings, three wattages and three prices that cannot be compared. The suppliers are not necessarily wrong. Each has filled the gaps in the enquiry with its own assumptions. This guide shows what to send so that the quotes are comparable, what a proper design quote contains, and how much the assumptions matter, using a worked example.

Who provides a lighting design

Source What you get Cost
Manufacturer Layout and lux calculation using its own fittings Usually included in the quotation
Distributor or contractor Design, supply and installation as one price Included in the project price
Independent lighting consultant A specification that any maker can quote against A design fee

For a single large warehouse, a manufacturer’s design is usually enough, as long as you give every bidder the same brief and ask for the same outputs.

The brief: twelve facts to send

  1. Dimensions. Length, width and clear height. A drawing is better than numbers.
  2. Mounting height. Where the fittings can hang: roof steel, trunking or cable tray, and at what height.
  3. Floor layout. Racking positions and heights, aisle widths, open areas, mezzanines, docks.
  4. Task and target lux for each area. Bulk storage, picking, packing and inspection need different levels.
  5. Surface colours. Walls, roof lining and floor: light, medium or dark.
  6. Supply. Voltage and frequency; single or three phase.
  7. Operating hours. Shifts per day and days per year. This decides how much efficacy and controls are worth.
  8. Environment. Temperature range, dust, moisture, corrosive air, any hazardous areas.
  9. Daylight. Rooflights or windows, and whether daylight dimming is wanted.
  10. Controls. Simple switching, occupancy sensors by aisle, dimming, or a central system.
  11. Emergency lighting. Whether it is part of this package.
  12. Existing installation. For a retrofit: the type, wattage, number and mounting points of the old lights.

Item 4 is the one most often missing. If you do not know the level, say what happens in each area and ask the supplier to propose levels to a named standard.

What a design quote should contain

Part What to look for
Layout drawing Every fitting position, row and spacing, to scale
Fitting schedule Model, wattage, lumens, beam angle, colour temperature, quantity
Calculated results Maintained average lux, minimum, and uniformity for each area
Assumptions Maintenance factor, surface reflectances, mounting height, working plane
Connected load Total kW and W/m²
Photometric data The file used for each fitting, on request
Controls proposal Sensor positions and switching groups
Commercial terms Price, lead time, warranty, certificates

If a quote gives only a quantity and a price, ask for the rest before comparing it with anything.

Worked example: 120 × 80 m at 12 m

Take a distribution warehouse of 120 × 80 m (9,600 m²) with fittings at 12 m, medium-coloured surfaces, and 200 W high bays at 100 lm/W. Our high bay lighting calculator gives, for open floor:

Target Fittings Grid Spacing Calculated average Load
150 lux 117 13 × 9 9.2 × 8.9 m 151 lux 23.4 kW, 2.4 W/m²
200 lux 165 15 × 11 8.0 × 7.3 m 213 lux 33.0 kW, 3.4 W/m²
300 lux 247 19 × 13 6.3 × 6.2 m 319 lux 49.4 kW, 5.1 W/m²

Open the example and enter your own building.

The step from 150 to 300 lux doubles the installation. This is why the target level must be in the brief: a bidder who assumes 150 lux will always look cheaper than one who assumes 200.

How assumptions move the count

Keep the building and the 200 lux target, and change one assumption at a time:

Assumption changed Fittings Difference
Baseline: medium beam, medium surfaces 165 —
Wide beam 176 +7%
Narrow beam 150 −9%
Dark walls and roof 176 +7%

The narrow beam looks like a saving, and at 12 m it can be a good choice. But narrow beams must be closer together to overlap: the calculator’s spacing limit drops from about 13.4 m to 10.1 m, and vertical surfaces such as rack faces receive less light. The lowest count is not automatically the best design.

Efficacy matters just as much. The example uses 100 lm/W. A fitting at 130 lm/W delivers the same light with about 23% less power, so check the lumens of each offered fitting, not only the watts. Our best LED high bay lights buying guide lists what to compare.

Open floor is not racking

The lumen method treats the building as an empty box. A racked warehouse is a set of narrow canyons:

  • the racks block light, so the rows must run along the aisles, one row above each;
  • aisle optics, long and narrow, put light on the rack faces and the floor instead of on the top of the racks;
  • the important value is often vertical illuminance on the labels, not horizontal lux on the floor;
  • the number of rows is fixed by the number of aisles, and the spacing along the aisle follows from the height.

A design for a racked building therefore needs the racking drawing. If the racking is not yet decided, ask for two designs: open floor now, and aisle layout later, using the same fittings on movable trunking.

Questions to ask each supplier

  1. What maintenance factor did you use, and what cleaning interval does it assume?
  2. What are the lumens and efficacy of the fitting at the stated colour temperature?
  3. What uniformity does the design reach in each area?
  4. Is the result for open floor or with the racking modelled?
  5. What is the total connected load?
  6. What is the warranty, and what does it cover: driver, LEDs, light output?
  7. Which certificates apply to this model, and can I see them?

On the last point: our CCC certificate covers the BGGKP50C factory light series from 60 W to 330 W. For other series we confirm the available certificates with the quotation. Ask every supplier for the same clarity.

Controls change the running cost more than the fitting

In large warehouses many aisles are empty most of the time. Occupancy sensors that dim each aisle to a low level when nobody is in it often save more energy than the difference between two good fittings. Ask each bidder to include a controls option, with the sensor positions on the drawing. See high bay occupancy sensors for how they work at height.

Retrofit or new layout

If the building already has lights at sensible positions, a one-for-one replacement saves the cost of new wiring. If the racking has changed since the lights were installed, the old positions are probably wrong and a new layout pays for itself in better light. Our warehouse LED lighting upgrade guide compares the two routes.

Common mistakes

Mistake Result
Asking for “a price for 200 W high bays” Quotes that cannot be compared
No target lux in the brief Each bidder picks a different level
Comparing fitting counts The cheapest design wins, not the best
Ignoring the maintenance factor Under-lit after two years
Sending no racking layout Rows above racks instead of aisles

What we provide

Send us the twelve facts above, or as many as you have. We reply with a layout, a fitting schedule from our LED high bay lights range, the calculated lux and uniformity, the connected load and the assumptions, so you can compare our quote with any other.

Sources

  1. EN 12464-1 — Lighting of work places, Part 1: Indoor work places
  2. BlueGreen OE — High bay and warehouse lighting calculator
  3. BlueGreen OE — UFO LED high bay GKP40F, product data

Frequently asked questions

What information do I need to get a warehouse lighting design quote?

The building length, width and mounting height, a racking or floor layout, the target lux for each area, the supply voltage, operating hours, wall and ceiling colours, any special conditions such as cold, dust or hazardous areas, and the controls you want.

Do suppliers charge for a lighting design?

Manufacturers usually prepare a layout and lux calculation as part of a quotation for their own fittings. Independent consultants charge a fee and specify fittings from any maker. We provide the design with our quotation.

How many high bay lights does a large warehouse need?

It depends on the area, height and lux level. For open floor of 120 × 80 m with fittings at 12 m, the lumen method gives about 117 fittings of 200 W for 150 lux, 165 for 200 lux and 247 for 300 lux.

How do I compare two lighting quotes with different numbers of fittings?

Compare the calculated result, not the count: maintained average lux, uniformity, total connected load in kW and the maintenance factor assumed. A quote with fewer fittings that assumes a maintenance factor of 0.9 is not equal to one that assumes 0.8.