Commercial LED Lighting Layouts: Office, Shop and Warehouse Worked Through
How to lay out LED lighting in commercial spaces: target lux, the lumen method, spacing limits, and three layouts calculated with our tool: an office, a shop floor and a warehouse.
Key points
- Every commercial layout starts from three inputs: the target illuminance for the task, the room size and mounting height, and the fitting's lumen output. The lumen method turns them into a fitting count; spacing limits turn the count into a grid.
- An 18 × 12 m open office at 500 lux needs 48 of our 36 W low-glare panels at 120 lm/W (about 600 lux); a 90 lm/W panel needs 63.
- A 20 × 15 m shop floor at 300 lux takes 99 downlights of 18 W on a 1.8 × 1.7 m grid; a 40 × 24 m warehouse at 9 m and 200 lux takes 24 high bays of 150 W.
- At low ceilings, spacing rather than light output often sets the count. Check the spacing-to-height ratio before buying higher-wattage fittings.
A good commercial lighting layout is not a guess at “one fitting every so many metres”. It comes from a short calculation that anyone can follow, and the same method works for an office, a shop or a warehouse. This guide explains the steps, then works through three typical spaces with our calculator so you can see where the numbers come from.
The four steps
- Choose the target illuminance. The task decides. EN 12464-1 lists values such as 500 lux for writing and reading in offices and 300 lux for general sales areas in shops. Warehouses for storage and picking are typically 100–200 lux.
- Count the fittings with the lumen method. Required lumens = target lux × area. Divide by the fitting’s lumens × utilisation factor (how much light reaches the working plane) × maintenance factor (light lost to ageing and dirt over time).
- Arrange them in a grid. Divide the count into rows and columns in proportion to the room’s length and width.
- Check the spacing. Each fitting has a maximum spacing, related to the mounting height above the working plane and its beam. If the grid spacing exceeds it, add rows or columns, even if the lumens are already enough.
The utilisation factor depends on the room index, a number that describes how wide and long a room is compared with its height. Large, low rooms have a high room index and use light efficiently; small, tall rooms have a low one and lose more light on the walls.
Our high bay lighting calculator carries out all four steps. It is named for high bays, but the method is the same for panels and downlights.
Example 1: open-plan office
An open office of 18 × 12 m with a 3 m ceiling, desks at 0.8 m, light-coloured surfaces and a target of 500 lux.
Using our 36 W low-glare office panel, which gives 4,320 lm at 4000 K (120 lm/W) with a 90° beam, the calculator gives:
| Result | 120 lm/W panel | 90 lm/W panel |
|---|---|---|
| Room index | 3.27 | 3.27 |
| Fittings | 48 (8 × 6) | 63 (9 × 7) |
| Spacing | 2.25 m × 2.0 m | 2.0 m × 1.7 m |
| Average illuminance | about 600 lux | about 568 lux |
| Power density | 8.0 W/m² | 10.5 W/m² |
The second column is our standard BG-MBC panel at 36 W and 90 lm/W, with a wider 120° beam. The more efficient panel saves 15 fittings and 2.5 W/m² in this room. Over a year of 2,500 office hours, that is about 1,350 kWh for one floor area of 216 m².
Notice that the efficient layout reaches 600 lux, not 500. The calculator reports that 30 W panels would be enough for 48 positions; the spacing limit at 2.2 m above the desks set the grid. In a real office, dimmable drivers or a daylight sensor bring the light down to the target and save the difference. Our article on commercial lighting control systems explains the options.
Example 2: shop floor
A shop floor of 20 × 15 m with a 3.5 m ceiling, light surfaces and 300 lux general lighting, before any display accent lighting.
With our BG-TDT downlight at 18 W and 90 lm/W, 90° beam, the calculator gives 99 downlights (11 × 9) at about 1.8 m × 1.7 m spacing, about 332 lux and 5.9 W/m².
Shops rarely use one even grid. A common approach is to use the general grid for circulation and lower-level shelving, then add accent lighting on feature walls and displays with track spots. The accent load is on top of the general lighting, so start with a slightly lower general level if the accent lighting is extensive. Our guides to LED downlight sizes and downlight beam angles help choose the fitting.
Example 3: warehouse
A warehouse of 40 × 24 m with 9 m to the roof and 200 lux at floor level, with block stacking rather than tall racks.
With our GKP40G heat-pipe high bay at 150 W and 130 lm/W, the calculator gives 24 fittings (6 × 4) at about 6.7 m × 6.0 m spacing, about 242 lux and 3.75 W/m².
With tall racking the grid gives way to rows over each aisle, because racks block light from fittings over the next aisle. Our warehouse lighting lux levels guide covers racked layouts.
Comparing the three
| Space | Target | Fittings | Power density |
|---|---|---|---|
| Office 18 × 12 m | 500 lux | 48 × 36 W panels | 8.0 W/m² |
| Shop 20 × 15 m | 300 lux | 99 × 18 W downlights | 5.9 W/m² |
| Warehouse 40 × 24 m | 200 lux | 24 × 150 W high bays | 3.75 W/m² |
Power density is a quick way to check a design against energy codes such as ASHRAE 90.1, which set maximum lighting power per square metre for each space type. If your figure is well above the code allowance, either the efficacy is low or the layout is over-lighting the space.
Layout rules of thumb
- Align with the furniture. Rows parallel to desks or aisles avoid glare and shadows.
- Keep fittings off the wall line. The first row is normally half a spacing from the wall.
- Mind glare in offices. Choose panels with controlled luminance for screen work.
- Plan switching by zone. Window rows, perimeter and interior zones should be controllable separately.
- Do not fill gaps with more watts. If spacing limits the count, use lower-wattage fittings in the same positions.
When to ask for a full photometric design
The lumen method gives an accurate average for regular rooms. For irregular shapes, very high uniformity requirements, or projects where the client needs a point-by-point report, we prepare a full photometric calculation with the fitting’s measured light distribution. Send us the drawings, ceiling heights and lux targets. For shops specifically, see our lumens per square foot for shops guide, and for offices, our LED troffer guide.
Sources
Frequently asked questions
How do you calculate a commercial lighting layout?
Multiply the target illuminance by the floor area to get the lumens needed on the working plane, divide by the fitting's lumen output, the utilisation factor and the maintenance factor to get a count, then arrange that count in a grid that respects the fitting's maximum spacing. Our high bay lighting calculator does these steps.
How far apart should LED panels be in an office?
With a 3 m ceiling and 0.8 m desk height, a spacing of about 2 m is typical for 600 × 600 mm panels to reach 500 lux with good uniformity. The exact figure depends on the panel's output and beam.
How many lux does a commercial space need?
Common values are 500 lux for offices and desk work, 300 lux for general retail sales areas, 100–200 lux for warehouses, and 750 lux or more for detailed inspection. Local codes and client specifications may set different values.
Should commercial lights run parallel to windows?
Rows parallel to the window wall make daylight dimming simple, because the row nearest the window can be switched or dimmed separately. Rows should also align with desks or aisles where possible.