Sports Lighting Cost: Fittings, Power and Running Cost by Level of Play

What sports lighting costs, worked out for a basketball hall and a badminton hall at 200 to 750 lux: fittings, connected kW, yearly kWh and how to cut the bill.

Key points

  • The level of play sets the cost: in our calculation a 36 × 22 m basketball hall needs 20 fittings for 200 lux training and 54 for 750 lux national matches.
  • Connected load rises from about 3 kW to almost 11 kW across those levels, and yearly energy at 2,000 hours from 6,000 to 21,600 kWh.
  • Running cost is connected kW × hours × tariff; check it against every quotation before comparing prices.
  • Switching by level of play (training, club, match) is the biggest saving after the LED fitting itself.

“How much will the lighting cost?” is usually the first question from a club, school or sports centre, and the honest answer is that it depends less on the brand of the fittings than on one decision: the level of play you design for. That decision sets the light level, the light level sets the number of fittings, and the number of fittings sets the purchase price, the installation work and the electricity bill. This guide puts numbers on each step for two typical indoor halls, using our own calculator, so you can see how cost moves before asking for quotations.

Level of play is the first cost decision

The European standard EN 12193 groups sports lighting into three classes. For indoor ball sports such as basketball, volleyball and handball, the usual horizontal illuminance values are about 200 lux for class III (training, school and recreational play), 500 lux for class II (club and league competition) and 750 lux for class I (national and international matches). For badminton the class III value is higher, about 300 lux, because the shuttle is small and fast.

Moving from class III to class I multiplies the light on the floor by three or four. It does not multiply the cost of the building, but it does multiply almost everything else in the lighting budget.

Example 1: a basketball hall

We took a 36 × 22 m hall, which holds one full basketball court with run-off and space for benches, with fittings at 10 m. We ran it through our high bay and warehouse lighting calculator with medium reflectances, a floor-level working plane, a maintenance factor of 0.8 and fittings of 130 lm/W, the efficacy of our heat-pipe high bays.

Level Target Fitting Fittings (grid) Average Connected load Energy at 2,000 h/year
Class III, training 200 lux 150 W 20 (5 × 4) 228 lux 3.0 kW 6,000 kWh
Between III and II 300 lux 150 W 28 (7 × 4) 319 lux 4.2 kW 8,400 kWh
Class II, club matches 500 lux 200 W 35 (7 × 5) 532 lux 7.0 kW 14,000 kWh
Class I, national matches 750 lux 200 W 54 (9 × 6) 820 lux 10.8 kW 21,600 kWh

The step from club to national level adds 19 fittings and almost 4 kW. That is why it pays to be honest about which matches the hall will really host.

Example 2: a four-court badminton hall

A 40 × 20 m hall with four badminton courts and fittings at 9 m, with the same assumptions:

Level Target Fitting Fittings (grid) Average Connected load Energy at 2,000 h/year
Recreational 200 lux 150 W 18 (6 × 3) 210 lux 2.7 kW 5,400 kWh
Class III 300 lux 150 W 28 (7 × 4) 326 lux 4.2 kW 8,400 kWh
Class II 500 lux 200 W 40 (8 × 5) 621 lux 8.0 kW 16,000 kWh
Class I 750 lux 200 W 50 (10 × 5) 776 lux 10.0 kW 20,000 kWh

These are counts for an even grid. In a real badminton hall the fittings go between and beside the courts, not above the playing lines, so the final layout can need a few more. Our badminton court lighting guide shows that placement.

The running cost formula

Every quotation for sports lighting should let you work out this line:

Yearly cost = connected kW × hours of use per year × tariff

At an example tariff of 0.15 per kWh, the basketball hall costs about 900 a year to run at training level and about 3,240 at national level, for 2,000 hours. Use your own tariff and hours: a school hall used after classes may run 1,000–1,500 hours a year, a commercial sports centre open every evening and weekend 3,000 or more.

Two quotations with the same lux figure can differ in connected load by 20–30% because of fitting efficacy and optics. Over ten years that difference is often worth more than the difference in purchase price, so ask each supplier for the connected load at your target level, not only the price per fitting.

Replacing metal halide

Many existing halls still use 400 W metal halide high bays. A typical example: 24 lamps drawing about 460 W each with ballast losses, used 8 hours a day. Replacing them with 150 W LED fittings in our LED retrofit savings calculator gives:

Item Metal halide LED
Energy per year 32,237 kWh 10,512 kWh
Saving 21,725 kWh (67%)
Saving per year, energy and maintenance about 3,690
Payback on the assumed fitting and installation cost about 12 months

The fitting and installation costs in this example are calculator inputs, not our prices; enter the figures from your quotation. Metal halide also takes minutes to restrike after a power dip, which matters during a match. See our metal halide to LED guide for wattage equivalents.

What else goes into the budget

The fittings are only part of the cost. A realistic budget for an indoor hall includes:

  • Fittings, scaled by the count in the tables above.
  • Mounting and access: brackets, cable trays and a lift or scaffold at 9–10 m. In an existing hall this can rival the cost of the fittings.
  • Cabling and switchgear, sized for the connected load and split into circuits by court or by level.
  • Controls: switching or dimming by level of play, and sensors in corridors and stores.
  • Ball protection: guards or impact-resistant covers on fittings above the courts.
  • Design: a photometric calculation that shows the average, the uniformity and the glare for the real layout.

Outdoor sports add poles, foundations and crossarms, which are covered in our guide to football pitch floodlighting cost.

Five ways to keep sports lighting cost down

  1. Design for the highest level, switch for the rest. Wire the fittings in groups so the hall runs at 200 lux for training and 500 or 750 lux only for matches. In the basketball example, training on 20 of 54 fittings uses 3 kW instead of 10.8 kW.
  2. Choose efficacy, not only wattage. A 130 lm/W fitting needs fewer units than a 100 lm/W one for the same lux.
  3. Use the right beam. Medium beams at 9–10 m put more light on the floor and less on the walls than wide beams.
  4. Light-coloured walls and ceilings raise the utilisation factor; dark surfaces in our calculator cut it noticeably.
  5. Avoid oversizing for “future” levels you will never host. Each step up the standard costs real fittings and kilowatts.

A note on uniformity and glare

The tables above are averages. EN 12193 also asks for a minimum ratio of the lowest to the average illuminance, and players look up at the ball, so glare control decides where fittings can go. Both are checked in the photometric calculation, and both can add a few fittings to the count. We lit two basketball arenas and a sports training hall with high-mounted LED fittings; see the sports hall lighting project and our gym lighting guide.

What to send for a cost estimate

Send us the hall dimensions and height, the sports played, the highest level of play you need and the hours of use per year. We will return a fitting count for each level, the connected load, a photometric calculation and a quotation for our LED high bay lights, so you can compare running costs as well as prices.

Sources

  1. BlueGreen OE — High bay and warehouse lighting calculator
  2. BlueGreen OE — LED retrofit savings calculator

Frequently asked questions

How much does it cost to light an indoor sports hall?

The cost follows the level of play. For a 36 × 22 m basketball hall our calculation gives about 20 LED fittings of 150 W for 200 lux training, 35 of 200 W for 500 lux club matches and 54 of 200 W for 750 lux national matches. Fittings, installation and controls scale roughly with that count.

How much electricity does sports lighting use?

Multiply the connected load by the hours of use. The same basketball hall draws about 3 kW at training level and 10.8 kW at national level; at 2,000 hours a year that is 6,000 and 21,600 kWh.

Is it cheaper to light a hall for training only?

Yes, but plan the fittings for the highest level you will need and switch down for training. Installing 750 lux and running it at 200 lux most evenings costs less than rebuilding the lighting later.

How fast does LED sports lighting pay back over metal halide?

In our example, 24 LED fittings of 150 W replacing 400 W metal halide lamps for 8 hours a day save about 21,700 kWh a year, which pays back in about a year at the tariff and fitting cost we assumed.