How to Read an Ex Marking: Ex db IIC T6 Gb, Ex ia IIC T4 Ga and Older Labels Decoded
A field guide to reading Ex markings on explosion-proof equipment: protection type, gas or dust group, temperature class, EPL, ATEX category and X or U suffixes, with real nameplates.
Key points
- An IEC Ex marking always reads in the same order: Ex, protection type, group, temperature class, equipment protection level (EPL).
- Ex db IIC T6 Gb means a flameproof enclosure, suitable for all gas groups, surface below 85 °C, for Zone 1 or Zone 2.
- Dust markings use group III and a surface temperature in °C instead of a T class, for example Ex tb IIIC T130 °C Db.
- An X after the certificate number means special conditions of use; a U means a component, not a complete product.
- Our BED series carries two markings on one label: Ex db eb mb IIC T4 Gb for gas and Ex tb IIIC T130 °C Db for dust.
The nameplate on an explosion-proof light, junction box or motor carries a short string such as “Ex db IIC T6 Gb”. Every character has a meaning, and two strings that look almost the same can allow very different installations. We read these labels every week when buyers send photos of fittings they want to replace. This guide walks through the order of the parts, what each one allows, and the older and regional formats you will still meet on site.
The order is always the same
Under IEC 60079-0, the marking for gas atmospheres is written in this sequence:
| Position | Example | What it tells you |
|---|---|---|
| 1 | Ex | The product is protected for explosive atmospheres |
| 2 | db | Protection type and its level (a, b or c) |
| 3 | IIC | Group: which gases (or dusts) it is designed for |
| 4 | T6 | Temperature class: the hottest surface allowed |
| 5 | Gb | Equipment protection level (EPL): which zones |
If you learn this order, any marking becomes readable. A product protected in more than one way lists several protection codes in position 2, separated by spaces.
Position 2: protection type and level
The letters name the method; the trailing letter (a, b or c) is the level of protection, with a the highest.
| Code | Method | Typical use on a light |
|---|---|---|
| da / db / dc | Flameproof enclosure: contains an internal explosion | LED chamber, lamp housing |
| eb / ec | Increased safety: no sparks or hot spots in normal use | Terminal box, connection chamber |
| ia / ib / ic | Intrinsic safety: energy too low to ignite | Sensors, portable lamps, control circuits |
| ma / mb / mc | Encapsulation: parts potted in compound | LED drivers, electronics |
| pxb / pyb / pzc | Pressurised enclosure | Control cabinets, analyser houses |
| ta / tb / tc | Dust protection by enclosure | Lights for Zone 20, 21 or 22 dust |
| op is / op pr / op sh | Optical radiation protection | Lasers, fibre optics |
Older labels without the trailing letter, such as “Ex d” or “Ex e”, come from earlier editions. “Ex d” corresponds to today’s db in most cases.
Position 3: the group
- Group I: underground mines with firedamp (methane) and coal dust.
- Group IIA, IIB, IIC: surface industries with gas. IIC covers every gas group, IIB covers IIA and IIB, IIA covers only IIA. Our IIB vs IIC gas groups article lists typical gases.
- IIB+H2: IIB plus hydrogen, but not acetylene or carbon disulphide.
- Group IIIA, IIIB, IIIC: dust. IIIA is combustible flyings, IIIB non-conductive dust, IIIC conductive dust. IIIC covers all three.
Position 4: the temperature class
For gas, T1 to T6 set the maximum surface temperature: T1 450 °C, T2 300 °C, T3 200 °C, T4 135 °C, T5 100 °C, T6 85 °C. The class must be below the ignition temperature of every gas present. Our T3 vs T4 article explains how to pick one.
For dust, the label gives the actual maximum surface temperature in degrees, for example T130 °C. The installer then checks it against the dust’s cloud and layer ignition temperatures with the safety margins the code requires.
Position 5: the EPL
| EPL | Zone (gas) | EPL | Zone (dust) |
|---|---|---|---|
| Ga | Zone 0, 1, 2 | Da | Zone 20, 21, 22 |
| Gb | Zone 1, 2 | Db | Zone 21, 22 |
| Gc | Zone 2 only | Dc | Zone 22 only |
Mining equipment uses Ma and Mb. The EPL is the quickest check against the area drawing: a Gc light in a Zone 1 area is not allowed, however good the rest of the marking looks. If your drawings use Class and Division instead of zones, see our Class/Division vs Zone comparison.
Real nameplates, decoded
Our BED series: the BED explosion-proof light is marked
Ex db eb mb IIC T4 Gb / Ex tb IIIC T130 °C Db, IP65
Reading it left to right: a flameproof LED chamber (db), an increased-safety terminal box (eb) and an encapsulated driver (mb); suitable for all gas groups (IIC); surfaces below 135 °C (T4); Zone 1 or 2 (Gb). The second line covers conductive dust (IIIC) with a maximum surface of 130 °C, for Zone 21 or 22 (Db). The certificate behind it is ZJEx23.0914, issued under China’s GB 3836 standards, which follow IEC 60079.
Ex db IIC T6 Gb: a flameproof fitting for any gas group, with a cooler surface limit of 85 °C. Our BDE507 and the BAD8599 floodlight carry markings of this kind; their certificates are supplied with the quotation.
Ex ia IIC T4 Ga: intrinsically safe, highest level, any gas, 135 °C limit, and Ga, so it may go into Zone 0, for example inside a tank. Lights rarely reach Ga because a useful lumen output needs more energy than intrinsic safety allows. Our intrinsically safe vs explosion-proof guide covers the trade-off.
Ex tD A21 IP66 T80 °C: an older dust marking from the IEC 61241 series. “tD” is protection by enclosure, “A21” means practice A, suitable for Zone 21, and T80 °C is the surface limit. Today the same equipment would be written as Ex tb IIIC T80 °C Db. You will see the old form on many fittings still sold, including some on our own site.
EEx d IIC T6: the European format used before 2003. The double E stood for European standard. It has no EPL; at the time, the zone was implied by the protection type.
The ATEX prefix
Products sold in Europe also carry the ATEX marking before the IEC string, for example:
⟨Ex⟩ II 2 G Ex db IIC T6 Gb
“II” is the equipment group (surface industry), “2” is the category (roughly equal to EPL b), and “G” means gas (D for dust). The category and the EPL should agree; if a label says category 3 but Gb, ask why before you install it.
Suffixes on the certificate number
- X, as in “IECEx ABC 21.0001X”: specific conditions of use apply. Typical ones are a limited impact resistance, a required cable gland type or a fixed mounting orientation.
- U: a component certificate, such as an empty enclosure or a terminal block. A U-certified part is not a finished product and cannot be installed alone.
Five checks before you accept a label
- Does the EPL match the zone on the area classification drawing?
- Does the group cover every gas or dust listed for that area?
- Is the temperature class below every gas ignition temperature, at the site’s highest ambient?
- Does the ambient range on the label (default −20 °C to +40 °C if not shown) cover your site?
- Is the certificate number traceable, and are its conditions (X) acceptable?
Our ratings explained article and the d2G4 guide cover the other formats you may see on older equipment. If you send us a photo of a nameplate and your area drawing, we will tell you which of our fittings matches it and which certificate comes with it.
Sources
Frequently asked questions
What does Ex db IIC T6 Gb mean?
Ex = explosion protected; db = flameproof enclosure at protection level b; IIC = suitable for the most easily ignited gases, including hydrogen and acetylene; T6 = maximum surface temperature 85 °C; Gb = equipment protection level for Zone 1 (and therefore Zone 2).
What does Ex ia IIC T4 Ga mean?
It is intrinsically safe equipment at the highest level, ia, for group IIC gases, with surfaces below 135 °C, and EPL Ga, which allows use in Zone 0, where an explosive atmosphere is present continuously or for long periods.
Why are there two markings on one explosion-proof light?
One covers gas atmospheres and the other covers combustible dust. A light used in a grain plant or a coal handling area needs the dust marking (group III, EPL D) as well as or instead of the gas marking.
What does the X after a certificate number mean?
It means the certificate lists specific conditions of use, such as an impact limit, a cable entry type or a reduced ambient range. The installer must read the certificate, not only the label.
Is an old 'EEx d IIC T6' marking still valid?
It was the pre-2003 European format. Equipment installed under it can stay in service if it is maintained and the area classification has not changed. New purchases should carry the current Ex marking with an EPL.