d2G4 Explosion-Proof Rating: What It Means and How It Compares with Ex d IIB T4
What the d2G4 explosion-proof marking means, how Japan's explosion classes and ignition degrees map to IEC gas groups and T classes, and how our own fittings' markings compare.
Key points
- d2G4 is the older Japanese marking: d = flameproof enclosure, 2 = explosion class 2, G4 = ignition degree G4.
- Its nearest IEC equivalent is Ex d IIB T4: explosion class 2 sits close to gas group IIB, and G4 covers gases igniting between 135 °C and 200 °C, the same band as T4.
- The two systems use different test methods, so the mapping is a guide, not an automatic substitution; the authority having jurisdiction decides.
- A IIC T4 light, such as our BED series (Ex db eb mb IIC T4 Gb), meets or exceeds the d2G4 gas and temperature requirements on paper, but Japan still requires a Japanese type-examination certificate.
Buyers sometimes send us an old drawing or a maintenance list with a light marked “d2G4” and ask what to replace it with. The marking comes from the Japanese system that was used widely in Japan and in plants built by Japanese contractors in Asia. It predates the IEC-style “Ex d IIB T4” marking now used almost everywhere, including in Japan’s newer standards. This guide decodes d2G4, maps it to the IEC system and shows where our own fittings sit.
Decoding d2G4
The marking has three parts:
| Part | Meaning | Notes |
|---|---|---|
| d | Flameproof enclosure | Same idea as IEC “d”: the housing withstands an internal explosion and cools escaping gas through its joints |
| 2 | Explosion class 2 | Gases of medium explosion propagation, such as ethylene |
| G4 | Ignition degree G4 | Gases whose ignition temperature is between 135 °C and 200 °C |
Other Japanese protection symbols include e (increased safety), i (intrinsic safety), o (oil immersion) and f (pressurised). You may see markings such as “e G3” or “d3aG4”. The letter after the 3 in the second example narrows the class to specific gases (3a for hydrogen and water gas, for instance).
Mapping to the IEC system
The IEC system describes the same two properties with different labels:
| Japanese | Nearest IEC | Typical gases |
|---|---|---|
| Explosion class 1 | Group IIA | Methane (in industry), propane, petrol vapour |
| Explosion class 2 | Group IIB | Ethylene, many ethers |
| Explosion class 3 | Group IIC | Hydrogen, acetylene, carbon disulphide |
| G1 | T1 (450 °C) | Gases igniting above 450 °C |
| G2 | T2 (300 °C) | 300–450 °C |
| G3 | T3 (200 °C) | 200–300 °C |
| G4 | T4 (135 °C) | 135–200 °C |
| G5 | T5 (100 °C) | 100–135 °C |
So d2G4 corresponds most closely to Ex d IIB T4. Our ATEX IIB vs IIC gas groups and ATEX T3 vs T4 temperature class articles explain the IEC side in detail.
There is one important difference. The IEC temperature class is a limit on the equipment’s surface temperature, chosen to stay below the gas’s ignition point. The Japanese ignition degree is written as a property of the gas. In practice both point to the same band, but the wording matters when you read a certificate. Likewise, the explosion classes and gas groups are based on gap tests that are not identical, so a gas at the edge of a class may fall differently. The site’s area classification and the authority having jurisdiction have the final say.
Where our fittings sit against d2G4
Using the mapping above, here is how our explosion-proof lights compare on paper:
| Model | Ex marking | Gas group vs class 2 | Temperature vs G4 | Certificate |
|---|---|---|---|---|
| BED series, 30–600 W | Ex db eb mb IIC T4 Gb | IIC, covers class 2 gases | T4, matches G4 | Our own, ZJEx23.0914 (GB 3836) |
| BDE507, 20–70 W | Ex d IIC T6 Gb | IIC, covers class 2 gases | T6, stricter than G4 | Provided with the quotation |
| ExF, 50–150 W | Ex d IIB T6 Gb | IIB, matches class 2 | T6, stricter than G4 | Provided with the quotation |
The BED series is the only one covered by our own explosion-proof certificate. Its certificate was issued under China’s GB 3836 standards, which follow IEC 60079. It is not an ATEX, IECEx or Japanese certificate.
What this means in practice: if your site is outside Japan and accepts IEC-aligned certificates, a light marked IIB or IIC and T4 or better is the usual replacement for d2G4. If the site is in Japan, the replacement must carry a Japanese type-examination certificate, whatever its marking. We do not hold one, and we say so in our quotations.
Replacing an old d2G4 light: a checklist
Old d2G4 fittings are often metal halide or fluorescent lights from the 1990s or 2000s. When replacing them with LED:
- Read the area classification, not just the old label. Processes change. A unit that once handled only ethylene may now handle hydrogen, which needs IIC.
- Check the zone. Japanese drawings use Zone 0, 1 and 2 (or the older “special”, “class 1” and “class 2” hazardous places). For Zone 1 the IEC equipment protection level is Gb.
- Confirm the temperature class at your ambient. Most fittings are rated for −20 °C to +40 °C or similar. Our ExF and BDE507 are rated to +50 °C. Above the rated ambient, the T class no longer applies.
- Match the cable entry. Older Japanese fittings often use metric or PF thread entries. Glands must be certified for the same protection type and fit the new thread.
- Compare light output, not watts. A 250 W metal halide lamp gives roughly 20,000 lamp lumens, but much less after its fitting’s losses. Our explosion-proof light specifications guide shows what to compare.
Worked replacement example
Take a hypothetical case: 24 d2G4 floodlights on a tank-farm walkway outside Japan, each with a 250 W metal halide lamp. The area is Zone 2, with ethylene and propane, and ambient temperatures up to 40 °C.
- Gas group: class 2 → IIB minimum. Both the ExF (IIB) and BED (IIC) qualify.
- Temperature: G4 → T4 minimum. ExF (T6) and BED (T4) qualify.
- Equipment protection level: Zone 2 → Gc or better. Both are Gb.
A 100 W ExF flood would be a candidate. At 110 lm/W that is about 11,000 lm per fitting from the complete luminaire. Each metal halide fitting draws about 288 W with ballast (15 % loss), so the 24 lights would fall from about 6.9 kW to 2.4 kW. Our LED retrofit savings calculator puts the energy saving at about 65 % at 12 hours a night. Before ordering, the site’s inspector should confirm that IEC-aligned markings and the offered certificate are accepted there.
Common questions on related markings
- “d2G3” maps to Ex d IIB T3: same gas class, but only for gases igniting above 200 °C.
- “d3nG4” is explosion class 3 for all class 3 gases, close to Ex d IIC T4.
- “e G3” is increased safety for G3 gases, close to Ex e II T3.
Our explosion-proof light ratings explained article covers the IEC side of each.
What to send us
Send a photo of the old nameplate, the area classification drawing or the gas list, the country of installation and the certificates your inspector accepts. We will tell you which of our fittings matches the marking and which certificate we can provide.
Sources
Frequently asked questions
What does d2G4 mean?
It is a Japanese explosion-proof marking. d means flameproof enclosure, 2 means explosion class 2 (gases such as ethylene), and G4 means ignition degree G4, for gases that ignite between 135 °C and 200 °C.
Is d2G4 the same as Ex d IIB T4?
They are close. Explosion class 2 is roughly gas group IIB, and G4 covers the same temperature band as T4. The test methods behind the classes differ, so the equivalence should be confirmed by the inspector or the authority for the site.
Can an IIC T4 light replace a d2G4 light?
On gas group and temperature, yes: IIC covers IIB gases and T4 matches G4. Whether it may be installed depends on the certificates the country requires. In Japan that is a Japanese type-examination certificate.
Are your explosion-proof lights certified in Japan?
No. Our BED series is certified under China's GB 3836 (certificate ZJEx23.0914), which is aligned with IEC 60079. It does not carry a Japanese, ATEX or IECEx certificate.