Escape Route Lighting: The 1 Lux Rule, Spacing and Maintained vs Non-Maintained
Escape route lighting requirements under EN 1838 and NFPA 101, where emergency lights must go, maintained vs non-maintained modes, and a worked check of a twin-head light over a corridor.
Key points
- EN 1838 asks for at least 1 lux on the centre line of escape routes up to 2 m wide, with a max:min ratio no worse than 40:1.
- NFPA 101 asks for an initial average of 1 foot-candle (about 10.8 lux) along the egress path, falling to no less than 0.6 fc average after 90 minutes.
- Maintained emergency lights are on all the time; non-maintained ones light only when the mains fails. Exit signs are usually maintained.
- Our worked check shows one 400 lm head with a 30° beam, mounted at 2.5 m, gives about 4.3 lux on the floor 10 m away, comfortably over 1 lux.
- Emergency lights go within 2 m of every exit door, stair, change of direction, intersection and fire-fighting point.
When the mains fails, escape route lighting has one job: to let people see the floor, the turns and the exits well enough to leave without falling or panicking. The rules are short, but the vocabulary (maintained, non-maintained, sustained, open area, high-risk task area) confuses many buyers. This guide explains the numbers, where the fittings must go and how to check a light against the 1 lux rule. We use our own emergency fittings as the example.
The numbers that apply
| Requirement | EN 1838 (Europe and many other countries) | NFPA 101 (United States) |
|---|---|---|
| Escape route illuminance | ≥ 1 lux on the centre line (routes up to 2 m wide) | Initial average ≥ 1 fc (10.8 lux); minimum ≥ 0.1 fc at any point |
| Uniformity | Max:min ≤ 40:1 | Max:min ≤ 40:1 |
| Open (anti-panic) areas | ≥ 0.5 lux over the floor, excluding a 0.5 m border | Covered by the same egress rules |
| High-risk task areas | ≥ 10 % of normal illuminance, and at least 15 lux | Not set separately |
| Duration | ≥ 1 h (often 3 h by national rules) | ≥ 90 min |
| Response time | 50 % in 5 s, 100 % in 60 s | Within 10 s |
| End of duration | — | Average ≥ 0.6 fc and minimum ≥ 0.06 fc after 90 min |
Note how different the two systems are in level: the American code asks for roughly ten times the European centre-line minimum. A light that passes EN 1838 at a given spacing may fail NFPA 101 at the same spacing.
Where emergency lights must go
Both codes require a light near the points where people are most likely to trip or hesitate. EN 1838 says within 2 m horizontally of:
- each exit door used in an emergency;
- each staircase, so that every flight receives direct light;
- any other change in floor level;
- each change of direction;
- each intersection of corridors;
- outside each final exit, to a place of safety;
- each first-aid point;
- each piece of fire-fighting equipment and each call point (with 5 lux vertical on the equipment).
Mandatory signs (exit signs) also have to be lit. Our green vs red exit signs article covers the colour rules by country.
Maintained, non-maintained and combined
| Mode | Normal operation | On mains failure | Typical use |
|---|---|---|---|
| Maintained | Lamp on | Lamp stays on from battery | Exit signs, cinemas, shops, public buildings |
| Non-maintained | Lamp off | Lamp lights from battery | Corridors, stairs and plant rooms with normal lighting |
| Combined (sustained) | One lamp on mains | A second lamp lights from battery | Signs and fittings with two light sources |
Maintained mode costs a little more energy but shows at a glance that the light works. In buildings where the normal lighting may be switched off while people are present, such as theatres, maintained signs are usually required. Non-maintained fittings are cheaper to run and suit back-of-house areas. Our emergency light types guide covers self-contained and central-battery systems as well.
Worked check: one twin-head light over a corridor
Our BG-FBYJ10A is a twin-head emergency light for hazardous areas: 10 W, more than 80 lm/W, two 30° heads, 2 hours of battery operation, marked Ex d IIC T4. How far down a corridor does one head reach 1 lux?
Assumptions, stated so you can check them:
– Each head emits 400 lm (half of 10 W × 80 lm/W), spread evenly inside its 30° beam.
– The light is mounted at 2.5 m and the head is aimed at a point on the floor 10 m away.
Step by step:
1. Solid angle of a 30° cone: 2π × (1 − cos 15°) = 2π × 0.0341 = 0.214 sr
2. Beam intensity: 400 lm ÷ 0.214 sr = about 1,870 cd
3. Distance to the aiming point: √(10² + 2.5²) = 10.3 m
4. Cosine of the angle of incidence on the floor: 2.5 ÷ 10.3 = 0.243
5. Floor illuminance: 1,870 × 0.243 ÷ 10.3² = about 4.3 lux
So at 10 m the head gives about four times the EN 1838 minimum. Even if the emergency-mode output were only a quarter of the rated output, the point would still receive about 1.07 lux. Emergency output is often lower than mains output, so ask for the emergency lumen figure and the photometric file before the final layout. The simple estimate tells you whether a fitting is in the right range before the detailed check.
Under NFPA 101, the same corridor needs an average of 10.8 lux. Here the single head would not be enough along a 20 m stretch, and more fittings or a higher-output fitting would be needed.
Signs: our exit sign example
Our BG-XFYJ exit sign (3 W and 5 W) switches to its battery in under 2 seconds and runs for at least 90 minutes after a 24-hour charge. That meets NFPA 101’s 90 minutes and EN 1838’s 1-hour minimum, but not a 3-hour national requirement. It is IP40, for dry indoor areas only. Our wet location emergency light guide covers damp and outdoor routes.
Common mistakes we see in layouts
- Only the exit doors are lit. Changes of direction and stairs are forgotten, and the route between them falls below 1 lux.
- Normal light levels used to justify spacing. The emergency output, not the mains output, decides the spacing.
- Duration chosen without checking the building type. A 1-hour fitting in a hotel that needs 3 hours fails inspection.
- Hazardous areas lit with standard emergency fittings. If the route passes through a classified zone, the emergency lights there must be rated for it. Our explosion-proof emergency exit lights guide covers that case.
- No test plan. Monthly function tests and annual full-duration tests are needed to keep the system compliant; see emergency light testing.
What to send us
Send a floor plan with the escape routes marked, the code your building follows, the required duration and whether any route crosses a hazardous area. We will suggest positions and fittings, and check the spacing against the emergency-mode output.
Sources
Frequently asked questions
What is the minimum lux level for escape route lighting?
Under EN 1838, at least 1 lux along the centre line of escape routes up to 2 m wide, with the central band of at least half the route width lit to at least 50 % of that value. Under NFPA 101, an initial average of 1 foot-candle (about 10.8 lux) and at least 0.1 fc at any point.
What is the difference between maintained and non-maintained emergency lighting?
A maintained emergency light is on all the time and stays on from its battery when the mains fails. A non-maintained light is off in normal use and lights only on mains failure. Maintained mode is used where the building is occupied by the public or where the light also acts as normal lighting or as a sign.
How long must escape route lighting last?
EN 1838 sets a minimum of 1 hour. Many countries and building types require 3 hours, for example where people sleep or where the building may be reoccupied right after a power cut. NFPA 101 requires 90 minutes.
How far apart should emergency lights be?
There is no single distance. Lights must be placed at each exit, stair, change of direction and intersection, and then spaced so that the route reaches the minimum lux between them. The spacing comes from the fitting's photometric data and mounting height.