T6 Temperature Class: When an Explosion-Proof Light Must Stay Below 85 °C
What a T6 rating means, which gases need it, why LED makes T6 easier, which of our Ex lights are T6, and a worked layout for a carbon disulphide store.
Key points
- T6 means the hottest surface of the equipment stays at or below 85 °C, the lowest limit in the T1–T6 scale.
- Very few gases need T6; carbon disulphide, with an ignition temperature around 90 °C, is the textbook case.
- Our BDE507, ExF, BAD8599 and BAD8501B are T6; the BED series under our own certificate is T4.
- In our calculator, an 8 × 6 m carbon disulphide store with a 3.5 m ceiling reaches about 176 lux with six 30 W BDE507 lights.
T6 is the strictest temperature class in the gas explosion-protection system, and it appears on more datasheets than projects actually need. Knowing when it is required, and when T4 is already enough, helps you choose fittings that are neither unsafe nor over-specified. This guide explains what T6 means, which gases need it, which of our lights carry it, and how many a typical T6 room needs.
The temperature class in one paragraph
Every flammable gas has an auto-ignition temperature: heat a surface above it and the gas ignites without a spark. The T class tells you the highest surface temperature a piece of equipment can reach. Choose a class whose limit is below the ignition temperature of every gas in the area.
| Class | Max surface temperature | Gases with ignition above |
|---|---|---|
| T1 | 450 °C | 450 °C |
| T2 | 300 °C | 300 °C |
| T3 | 200 °C | 200 °C |
| T4 | 135 °C | 135 °C |
| T5 | 100 °C | 100 °C |
| T6 | 85 °C | 85 °C |
Our T3 vs T4 article explains the scale in more depth and why T3 and T4 cover most plants.
Which gases need T6
Very few. IEC 60079-20-1 and NFPA 497 list the auto-ignition temperatures. Among common industrial materials, carbon disulphide stands out, with an ignition temperature around 90 °C, below the T5 limit of 100 °C. It is used in viscose rayon and cellophane production, rubber chemicals and some solvent processes.
For comparison, petrol vapour needs T3, diethyl ether T4, and propane and hydrogen only T1. If carbon disulphide or a similar low-ignition material is not on your area list, T6 is unlikely to be a requirement. It can still be a sensible choice for other reasons, as below.
Why T6 is easier with LED
A fluorescent or HID lamp in an enclosure gets hot. Reaching T6 with those meant low wattage, large housings or both. An LED fitting puts much less heat into the enclosure for the same light, and the heat is drawn away through an aluminium body, so T6 is reachable at useful wattages. That is why many LED Ex fittings are marked T6 even when sold for T3 or T4 areas.
There are good reasons to accept T6 when it costs nothing extra:
- Mixed sites. One fitting type covers every room, including the one solvent store that needs T6.
- Future changes. A process change that brings a new chemical does not force a lighting change.
- Hot climates. A fitting with temperature margin is less sensitive to ambient conditions, as long as its rated ambient range is respected.
Our T6 and T4 fittings
| Series | Marking | T class | Ambient | Power |
|---|---|---|---|---|
| BDE507 | Ex d IIC T6 Gb | T6 | −30 to +50 °C | 20–70 W |
| ExF | Ex d IIB T6 Gb | T6 | −30 to +50 °C | 50–150 W |
| BAD8599 floodlight | Ex d IIC T6 Gb | T6 | — | 50–600 W |
| BAD8501B ceiling light | Ex d IIC T6 Gb | T6 | — | 15–30 W |
| BED | Ex db eb mb IIC T4 Gb | T4 | — | 30–600 W |
The BED series is covered by our own certificate ZJEx23.0914 (GB 3836, IEC 60079-aligned; not ATEX or IECEx) and is T4, which suits most hydrocarbons, hydrogen included. It is not for carbon disulphide. For the T6 series, the certificate for the exact model is supplied with the quotation; check that the T6 marking and the ambient range on it match your area before ordering. Where the table shows a dash, the ambient range comes with the certificate.
Note the gas group as well as the T class. Carbon disulphide is classed with hydrogen and acetylene in group IIC, because its flame passes through very narrow gaps. The ExF is IIB, so despite its T6 rating it is not suitable for a carbon disulphide area. The BDE507, BAD8599 and BAD8501B are IIC and T6.
Worked example: a carbon disulphide store
An 8 × 6 m store for drums of carbon disulphide, Zone 1 IIC T6, ceiling at 3.5 m. Staff check labels and drum condition, so we aim for 150 lux.
The BDE507 at 30 W, 110 lm/W and a wide beam, in our high bay lighting calculator (open the example):
- 6 fittings in a 3 × 2 grid, 2.7 × 3.0 m apart;
- about 176 lux;
- 3.8 W per m².
The calculator also shows that 26 W would just reach 150 lux, so the 30 W size is the right step. For a room where the BAD8501B’s low profile suits better, the same method gives the count for its 15–30 W sizes.
Keep fittings away from the drum filling or decanting point if the layout allows. Carbon disulphide vapour is heavier than air and collects low, while fittings are high, but the T6 rating, not the distance, is what makes the fitting acceptable.
Things that can push a T6 fitting hotter
- Ambient above the rated range. A light rated for +40 °C installed next to a hot process pipe may not stay T6.
- Wrong wattage. Some ranges are T6 only up to a certain power, with T5 or T4 above it. Read the certificate for the exact model.
- Dust or insulation on the housing. It traps heat. Clean fittings on a schedule; see explosion-proof light maintenance.
Common mistakes
- Asking for T6 everywhere by default. It narrows the choice of fittings and can raise cost without adding safety in T3 or T4 areas.
- Reading the T class without the gas group. A IIB T6 light is not acceptable in a hydrogen or carbon disulphide area.
- Mixing up gas T classes and dust temperatures. Dust uses degrees, checked against the dust layer; see Class 2 Division 2 lighting.
What to send us
The area classification with gas list, groups and T classes, the ambient range, room sizes and mounting heights. We will propose fittings whose marking matches, a count from our calculator, and the certificate for each model.
Sources
Frequently asked questions
What does T6 mean on an explosion-proof light?
The maximum surface temperature of the equipment, inside or outside depending on the protection type, will not exceed 85 °C at the rated ambient temperature. It is the coolest class in the T1–T6 scale.
Which gases need T6 equipment?
Gases with an auto-ignition temperature between 85 °C and 100 °C. Carbon disulphide is the common industrial example. Most hydrocarbons, including petrol, propane and hydrogen, are covered by T3 or T4.
Can a T6 light be used where T4 is required?
Yes. A lower maximum temperature covers every higher class, so T6 covers T5, T4, T3, T2 and T1 areas. The reverse is not true.
Does T6 depend on ambient temperature?
Yes. The class is valid for the rated ambient range on the label, normally −20 °C to +40 °C unless stated otherwise. Our BDE507 and ExF are rated for −30 °C to +50 °C. A hotter ambient needs the manufacturer's confirmation.
Is T6 the same as T85 °C for dust?
No. Gas areas use T classes; dust areas use a maximum surface temperature in degrees, such as T80 °C or T130 °C, checked against the dust's cloud and layer ignition temperatures.