Class 2 Division 2 Lighting: Dust Areas Where a Cloud Is Not Normal
What Class 2 Division 2 means for lighting, how dust layers set the surface temperature limit, how it maps to Zone 22, and a worked layout for a flour bagging hall.
Key points
- Class 2 Division 2 is a combustible dust area where a dust cloud is not expected in normal work, but dust can settle on equipment and can be raised by a fault.
- Groups E, F and G sort the dust: metal, carbon and everything else (flour, grain, sugar, plastics, wood).
- The most important check is surface temperature against the dust layer's ignition point, not the gas-style T code.
- In our calculator, a 30 × 18 m flour bagging hall with fittings at 7 m needs fifteen BAD8599 floodlights; the 100 W size gives about 170 lux.
Dust plants are often lit as if they were ordinary factories, until someone notices a thick grey layer on top of every high bay. That layer is the reason Class 2 locations exist. Division 2 is the milder of the two divisions, but it is the one where settled dust on hot surfaces is most often overlooked. This guide explains what Class 2 Division 2 means, how to choose the surface temperature, how it lines up with Zone 22, and how many fittings a typical bagging hall needs.
The marking in three parts
- Class 2 — the hazard is combustible dust. Class 1 is gas; Class 3 is fibres such as cotton lint.
- Division 2 — a dust cloud is not expected in normal operation. Dust may still accumulate on equipment, and an abnormal event can put it in the air.
- Group E, F or G — the type of dust.
Where dust clouds are present during normal work, such as inside a mill or near an open bag-tipping station, the area is Division 1. Our Class 2 Division 1 lighting guide covers that case. This article concentrates on what changes when the area is Division 2.
Groups E, F and G
| Group | Dust | Typical sites |
|---|---|---|
| E | Metal: aluminium, magnesium, titanium | Powder coating, metal finishing, additive manufacturing |
| F | Carbon: coal, coke, carbon black | Coal handling, power plants, tyre and rubber plants |
| G | Other: flour, grain, starch, sugar, wood, plastics | Mills, feed plants, bakeries, woodworking, pellet plants |
Group E is the strictest: metal dust is conductive and burns very hot, and the NEC places Group E dust present in hazardous quantities in Division 1. Most lighting projects we quote for dust are Group G.
Why Division 2 is about settled dust
In a Division 2 hall, the dust that matters is usually the layer on top of the light, not the air around it. A layer insulates the housing, raises its temperature and can smoulder long before a cloud forms. When it is later disturbed, a smouldering layer can ignite a cloud. That is why the dust standards ask for:
- A dust-tight enclosure. The NEC calls it dust-ignitionproof (Division 1) or dust-tight (Division 2). The zone system uses protection by enclosure, “tb” or “tc”.
- A limited surface temperature. It must stay below the ignition temperature of the dust layer with a margin. NFPA 499 lists layer ignition temperatures for many dusts.
Layer ignition temperatures vary widely between dusts, and the same material can differ with particle size and moisture. Use the tested value for your actual dust, from NFPA 499 or a laboratory report, and apply the margin your installation code requires.
How it maps to the zone system
| Class/Division | Zone | Equipment level |
|---|---|---|
| Class 2 Division 1 | Zone 20 or 21 | Da or Db |
| Class 2 Division 2 | Zone 22 | Dc (Db also allowed) |
Dust groups in the zone system are IIIA (fibres), IIIB (non-conductive dust) and IIIC (conductive dust). A IIIC fitting covers all three. For the wider picture, see combustible dust lighting for Zones 21 and 22 and the Class/Division vs Zone conversion guide.
Our dust-marked fittings
| Series | Dust marking | Max surface temperature | IP | Power |
|---|---|---|---|---|
| BED | Ex tb IIIC T130 °C Db | 130 °C | IP65 | 30–600 W |
| BAD8599 floodlight | Ex tD A21 IP66 T80 °C | 80 °C | IP66 | 50–600 W |
| BAD8501B ceiling light | Ex tD A21 IP66 T80 °C | 80 °C | IP66 | 15–30 W |
The BED series is covered by our own certificate ZJEx23.0914 under China’s GB 3836 standards (IEC 60079-aligned). It is not a UL, CSA, ATEX or IECEx certificate. For the BAD8599 and BAD8501B, the certificate for the exact model is supplied with the quotation. The BDE507 and ExF have no dust marking and are not for dust areas.
An 80 °C surface temperature leaves more room below low layer-ignition dusts such as some starches and sugars. If your dust has a low layer ignition temperature, the T80 °C fittings are the safer starting point.
Worked example: a flour bagging hall
A 30 × 18 m hall where flour is packed from closed hoppers into bags. Dust settles on beams and fittings, but clouds occur only when a bag splits. The area is Class 2 Division 2 Group G (Zone 22, IIIB). Fittings hang at 7 m; the target is 150 lux for packing and labelling.
We used the BAD8599 at 120 lm/W, its minimum rated efficacy, with a medium beam. Our high bay lighting calculator returns (open the example):
- 15 fittings in a 5 × 3 grid, 6.0 m apart each way;
- about 255 lux with the 150 W size;
- 4.2 W per m².
The calculator also shows 88 W per fitting reaches 150 lux on that grid. The 100 W BAD8599 therefore gives about 170 lux on the same fifteen positions, for 1.5 kW in total. Fewer, larger fittings would leave dark patches between the racks and bagging lines; spacing is capped at about 7.4 m for a medium beam at this height.
A 12 × 8 m sieving room next to it, ceiling at 4.5 m and 200 lux, needs sixteen BAD8501B ceiling lights in a 4 × 4 grid: 258 lux with 30 W, and the calculator shows 25 W is enough (open the example).
Installation and housekeeping
- Mount where dust is least likely to build up. A sloped top or a pendant away from ledges sheds dust better than a fitting tucked against a beam.
- Seal the entries. Use certified glands and blank the unused entries; one open entry ruins the enclosure rating.
- Set a cleaning interval. Dust layers are usually limited to a few millimetres by the installation standard. Our explosion-proof light maintenance guide gives a checklist.
- Think about the whole circuit. Switches and junction boxes in the hall need the same dust protection; see hazardous area light switches.
Common mistakes
- Treating Division 2 as unclassified. The dust-tight and temperature rules still apply.
- Using the gas T code for dust. Dust uses a temperature in degrees and the layer test, not T1–T6.
- Ignoring the layer. A fitting that is cool in clean air can run much hotter under 5 mm of flour.
What to send us
The area drawing, the dust type with its cloud and layer ignition temperatures, room sizes, mounting heights and target lux. We will send a fitting count from our calculator, the model with its dust marking and certificate, and a plain answer on which listings we can supply.
Sources
Frequently asked questions
What is a Class 2 Division 2 location?
A place where combustible dust is handled but a dust cloud is not present in normal operation. Dust may still settle on surfaces, and a leak, a burst bag or a cleaning job can raise it. Bagging halls next to closed conveyors and silo top floors are typical.
Which dust groups are in Class 2?
Group E is metal dust such as aluminium and magnesium. Group F is carbon dust such as coal and carbon black. Group G covers the rest: flour, starch, grain, sugar, wood, plastics and chemicals.
What is the Zone equivalent of Class 2 Division 2?
Usually Zone 22 in the IEC and ATEX system, with dust group IIIA, IIIB or IIIC. Equipment protection level Dc is the minimum; a Db fitting meant for Zone 21 can also be used.
Can I use an IP65 industrial light in a Class 2 Division 2 area?
Not on IP rating alone. The fitting must be identified for the class, division and group, or for Zone 22 with the right dust group, and its maximum surface temperature must suit the dust layer. An ordinary IP65 high bay has no such marking.
Which of your lights are marked for dust?
The BED series (Ex tb IIIC T130 °C Db) under our own certificate, and the BAD8599 floodlight and BAD8501B ceiling light (Ex tD A21 IP66 T80 °C), whose certificates come with the quotation.