Hazardous Area Light Switches: Ex Switches, Remote Contactors and Photocells Compared

Four ways to switch lights in a hazardous area: a certified Ex switch, a contactor in the safe area, an intrinsically safe input or a photocell, with a load calculation for our BED lights.

Key points

  • A light switch makes a small arc every time it operates, so inside a hazardous area it must be certified for the zone or division, gas group and temperature class, like the luminaire.
  • The cleanest design is often to keep switching out of the area: a contactor in the safe-area panel, controlled by a timer, photocell or a certified push button at the door.
  • Twenty of our BED 150 W lights at 220 V draw about 15 A with a power factor of 0.9 assumed, which exceeds the rating of many Ex rocker switches; a contactor carries that load easily.
  • Emergency and escape lighting must stay on when the normal lighting is switched off, so its unswitched supply is wired separately.

Explosion-proof luminaires get most of the attention on a hazardous-area lighting job, but every circuit also needs a way to turn the lights on and off. A light switch is one of the few devices in a lighting system that makes an arc in normal use, so where it sits and how it is certified matters as much as the luminaire. This guide compares four ways to handle hazardous area light switches, and works through the load of a real circuit with our BED explosion-proof lights.

For the wiring rules behind the examples, see Class 1 Division 1 electrical requirements.

Why the switch is the risky part

A luminaire’s driver and LEDs can be encapsulated or enclosed so that nothing sparks in normal operation. A mechanical switch cannot avoid it: each time the contacts open under load, a small arc forms. In a Zone 1 or Division 1 area, that arc must happen inside an enclosure that can contain an internal explosion (flameproof, Ex d or “explosionproof”), or with energy so low it cannot ignite the gas (intrinsically safe, Ex i).

So the first design question is not “which Ex switch?” but “does the switch need to be in the hazardous area at all?”

Option 1: a certified Ex switch in the area

A local switch beside the door or at the equipment is what operators expect. In the area it must be:

  • certified for the zone or division (Zone 1 equipment also suits Zone 2);
  • certified for the gas group (IIC covers IIB and IIA; IIB covers IIA);
  • below the required temperature class;
  • installed with the right glands or conduit seals; for NEC installations, a seal within 18 in (450 mm) unless the switch is factory sealed.

Ex rocker and rotary switches are typically rated for a single lighting circuit. Check the rating against both the steady current and the driver inrush, which can be many times the steady current for a few milliseconds when a row of LED drivers switches on together.

Best for: small rooms, a few fittings, operator control at the point of use.

Option 2: a contactor in the safe area

The most common industrial design keeps all load switching outside the classified area:

  1. The explosion-proof lights are fed from a lighting panel in a control room or a non-classified electrical room.
  2. A contactor in that panel switches each lighting circuit.
  3. The contactor is controlled by a timer, a building management system, a photocell, or a push button.

If the push button must be in the hazardous area, it switches only the low-power control circuit. An Ex control station or an intrinsically safe input does that easily, and it never carries the lighting load.

Best for: process areas, tank farms, loading bays, anything with more than a handful of fittings.

Option 3: an intrinsically safe control input

Where operators want local control but the plant already uses intrinsically safe instrument wiring, a simple push button on an IS loop can signal the control system, which then operates the safe-area contactor. The field device is cheap and light, and live maintenance is permitted on IS circuits under the plant’s rules. Our comparison of intrinsically safe vs explosion-proof explains the trade-off.

Best for: plants with existing IS infrastructure and a DCS or PLC.

Option 4: photocells and timers

Outdoor hazardous areas such as tank farms, loading gantries and forecourts usually run dusk to dawn. A photocell mounted in a non-classified position, or a certified one inside the area, can drive the lighting contactor. An astronomical timer in the panel needs no outdoor sensor at all. Our photocell guide covers sensor placement and switching levels.

Best for: outdoor areas that need light all night, with no one to switch it.

The four options side by side

Option Arcing device in the area? Local control Load capacity Typical cost driver
Ex switch in the area Yes, certified enclosure Yes One small circuit Certified switch, seals
Safe-area contactor No Via control input Many circuits Panel space, control wiring
IS push button + contactor No (energy-limited) Yes Many circuits IS barrier, control system
Photocell or timer + contactor No, if sensor is outside No Many circuits Sensor or timer

A load check with our BED series

Suppose a compressor house needs 20 luminaires of 150 W from our BED explosion-proof series, rated AC 220 V and marked Ex db eb mb IIC T4 Gb under our certificate ZJEx23.0914.

  • Total power: 20 × 150 W = 3,000 W
  • Current at 220 V with a power factor of 0.9 assumed: 3,000 ÷ (220 × 0.9) ≈ 15.2 A

That steady current is already above the rating of many Ex rocker switches, before inrush. Two practical answers:

  • Split and switch locally: two circuits of ten lights, about 7.6 A each, each with its own certified switch rated for the current and inrush.
  • Switch remotely: one or two contactors in the safe-area panel, with a single Ex push-button station at the door as the control input.

The second option puts no load-switching arc in the area and is easier to extend later. With larger fittings the case gets stronger: eight 200 W lights or twelve 100 W lights draw 8.1 A and 6.1 A respectively on the same assumptions, and most real areas mix several groups.

Emergency and escape lighting

Escape lighting must stay available when normal lighting is switched off. Feed emergency luminaires from an unswitched supply so the internal charger keeps the battery full, and switch only their maintained lamp, if they have one. If an emergency fitting goes into emergency mode every time someone turns the lights off, its battery will be flat when it is needed. Our emergency light installation guide covers the unswitched live and test switch, and explosion-proof emergency lighting covers duration and placement in hazardous areas.

Installation checks

  • Every switch, push button and junction box in the area carries a marking that matches the area classification drawing.
  • Cable glands or seals at each entry match the equipment’s certificate.
  • Covers are fully closed with all bolts in place; a missing bolt defeats a flameproof joint.
  • Control and power wiring are labelled so maintenance staff isolate the right circuit before opening any enclosure.

Our installation checklist for explosion-proof lights gives the luminaire-side checks.

What to send us

Send the area classification, gas group and temperature class, the number and power of fittings, supply voltage, and how you want to control them. We will propose circuit groups and suggest where switching should sit, and confirm which certificate covers each fitting we supply.

Sources

  1. IEC 60079-14 — Explosive atmospheres: electrical installations design, selection and erection
  2. NFPA 70, National Electrical Code — Article 501
  3. BlueGreen OE — Explosion-proof LED light, BED series (certificate ZJEx23.0914)

Frequently asked questions

Do I need an explosion-proof light switch in a hazardous area?

Yes, if the switch is inside the classified area. It must carry a marking for the zone or division, gas group and temperature class of the area. The alternative is to place the switching device outside the area and control it from there.

Can a normal switch be used just outside the hazardous zone?

Yes, if it is genuinely outside the classified boundary on the area classification drawing. Many sites place the light switch or contactor panel in a control room or at the safe-area side of the door for that reason.

Can a photocell switch lights in a hazardous area?

A photocell mounted inside the area must itself be certified. More often the photocell is mounted in a non-classified spot and drives a contactor in the safe-area panel, which switches the explosion-proof lights.

What current rating should an Ex switch have?

At least the circuit current with margin, plus allowance for LED driver inrush. For larger groups of lights, use the switch as a control input to a contactor rather than switching the load directly.