LED Panel Lights for Corridors: Size, Spacing and How Many You Need
Choosing LED panel lights for corridors: why narrow corridors need more light per square metre, calculated layouts for 2 m and 2.4 m corridors, panel sizes, sensors and emergency lighting.
Key points
- Corridors are lit at about 100 lux in EN 12464-1, but their narrow shape wastes light on the walls: in our calculator a 30 × 2 m corridor has a utilisation factor of about 0.41, against about 0.68 for an open office.
- For that 30 m corridor with a 2.8 m ceiling, 13 panels of 18 W (300 × 300 mm) in one row at about 2.3 m spacing give about 116 lux.
- A 40 × 2.4 m corridor with a 3 m ceiling needs 15 panels of 24 W (300 × 600 mm) at about 2.7 m spacing for about 120 lux.
- Occupancy sensors with a low standby level cut corridor energy sharply, and some panels on the escape route need emergency packs.
Corridors look like the simplest space in a building to light, and they are often the first place where an office or hospital looks gloomy. The reason is their shape. A long, narrow room sends much of each fitting’s light onto the walls, so a layout copied from an open office comes out darker than expected. This guide explains why, then gives calculated panel layouts for two common corridors.
Why corridors need more light per square metre
The lumen method uses a utilisation factor (UF), the share of the fitting’s light that reaches the floor or working plane. UF depends on the room index:
Room index K = (length × width) ÷ (mounting height above the plane × (length + width))
A 10 × 8 m office with a 2.8 m ceiling and desks at 0.75 m has K ≈ 2.2. A 30 × 2 m corridor lit to the floor, with the same ceiling, has K ≈ 0.67. In our lighting calculator, that gives:
| Space | Room index | Utilisation factor |
|---|---|---|
| Open office 10 × 8 m | about 2.2 | about 0.68 |
| Corridor 30 × 2 m | about 0.67 | about 0.41 |
So in the corridor only about 41% of the light reaches the floor directly or by reflection, compared with 68% in the office. Light-coloured walls help a lot here, because the walls receive much of the light and reflect it back. Dark walls or timber panelling can push the UF lower still.
Worked example 1: a 2 m corridor
A 30 m long, 2 m wide office corridor with a 2.8 m ceiling, light walls, lit to 100 lux on the floor. Using our BG-MBC LED panel at 90 lm/W:
| Panel | Size | Lumens | Number | Spacing | Average lux | W/m² |
|---|---|---|---|---|---|---|
| BG-MBC18 | 300 × 300 mm | 1,620 | 13 | 2.3 m | 116 | 3.9 |
| BG-MBC24 | 300 × 600 mm | 2,160 | 12 | 2.5 m | 143 | 4.8 |
The 18 W option meets the target closely with a single row of small panels. The 24 W option gives more light than needed; it would suit a corridor with darker finishes or a higher target, or could be dimmed to about 70% to save energy.
Worked example 2: a 2.4 m corridor
A 40 m long, 2.4 m wide corridor in a school or hotel, 3 m ceiling, light walls, 100 lux on the floor. The calculator gives a UF of about 0.44 and:
- 15 panels of 24 W (300 × 600 mm) in one row, at about 2.7 m spacing
- About 120 lux average, 3.75 W/m², 360 W in total
Mount 300 × 600 panels with their long side across the corridor. That spreads the light towards the walls, where people look, and reduces the “runway” effect of a line of bright rectangles stretching into the distance.
Layout tips
- One row down the centre for corridors up to about 2.4–2.8 m wide. Two rows only for wide corridors and lobbies.
- Light the ends and junctions. Place panels near corridor ends, doors, lift lobbies and changes of direction, even if that breaks the regular spacing.
- Watch the walls. Notice boards, signs and doors should be visible. Light walls make a corridor look brighter at the same lux.
- Avoid glare at the end of long corridors. Panels with a good diffuser, or a low-glare optic such as our low-glare 600 × 600 panel in wider spaces, are more comfortable than bare LED strips.
Panels, downlights or battens?
| Fitting | Good for | Watch out for |
|---|---|---|
| Panels (300 × 300 / 300 × 600) | Offices, schools, hotels with grid or plaster ceilings | Choose sizes that fit the ceiling grid |
| Downlights | Hotels and premium offices | Use wide beams (90°+) so pools overlap; see our downlight beam angle guide |
| Battens | Back-of-house, plant corridors, car park links | IP rating for damp areas; see our LED batten lights guide |
| Linear pendants | High-ceiling corridors and atria | Need a ceiling height that allows suspension |
Sensors and dimming
Corridors are the clearest case for occupancy control:
- Corridor-hold or dim-to-standby. Lights stay at 10–20% when the corridor is empty and rise to full when someone enters. This avoids walking into a dark corridor and still saves most of the energy.
- Daylight linking where corridors have windows.
- Zoning. Group panels in sections of 10–15 m so only the occupied section brightens.
Dimmable panels are needed for dim-to-standby; our guide to dimmable LED panel lights explains the driver options (0–10 V, DALI, triac).
Emergency lighting
Corridors are escape routes. Emergency lighting can come from separate emergency luminaires or from some of the corridor panels fitted with emergency packs. In either case, the escape route needs a minimum level along its centre line during a power failure, and fittings near exits, changes of direction and fire equipment. Our guide to LED flat panels with emergency backup covers how emergency packs work in panels and how long they run.
Energy check
The first example uses 13 × 18 W = 234 W for 60 m², or 3.9 W/m². With dim-to-standby sensors that hold the panels at 20% for most of the time an office corridor is empty, the average load can fall well below half of that. Compare with older fluorescent corridor lighting, where a similar corridor often carried two to three times the connected load.
What to send us
The corridor lengths, widths and ceiling heights, the ceiling type (grid or plaster), the wall finishes and the required lux. We will return a panel layout with counts, spacing and load, and mark which panels need emergency packs. For general rooms, our guide to LED flat panel lights covers sizes and specifications.
Sources
Frequently asked questions
What size LED panel is best for a corridor?
For corridors up to about 2.4 m wide, 300 × 300 or 300 × 600 mm panels in a single row along the centre suit the proportions and fit common ceiling grids. 600 × 600 panels work in wider corridors and lobbies; in narrow corridors they are spaced so far apart that the light becomes patchy.
How many lux does a corridor need?
EN 12464-1 gives 100 lux for corridors and circulation areas in most buildings, with higher values where there is vehicle traffic or in some healthcare settings. Stairs usually need about 150 lux. Check the local code and the building type.
How far apart should panel lights be in a corridor?
Typically 2–3 m for a single row at ceiling heights of 2.6–3 m, as in our examples at 2.3 m and 2.7 m. Keep the first panel within about half a spacing of each end and close to doors and junctions.
Should corridor lights be on sensors?
Usually yes. Corridors are often empty. Sensors that dim the lights to 10–20% when no one is there, rather than switching them off, keep the corridor safe and comfortable while saving most of the energy.