Emergency Light Test Button Not Working? A Step-by-Step Fault Finder

Why an emergency light does nothing when you press the test button: charging time, battery faults, permanent-live wiring, failed switches and drivers, with a fault-finding table and battery checks.

Key points

  • Before suspecting a fault, check the light has been charging long enough. Our BG-XFYJ exit sign, for example, needs up to 24 hours to charge fully after installation or a long discharge.
  • If nothing happens at all when you press the button, the usual causes are a missing permanent live, a flat or disconnected battery, or a failed test switch.
  • If the light comes on but dies within minutes, the battery is worn out. A 3 W sign that must run 90 minutes needs at least 4.5 Wh delivered at the end of the battery's life.
  • Always isolate the supply before opening a fitting. In hazardous areas, only a competent person may open an explosion-protected emergency light.

You press the test button on an emergency light and nothing happens, or the light flickers and goes out. Either way the light would fail in a real power cut, so it needs fixing before the next inspection. This guide goes through the causes in the order they are most likely, with the checks an electrician or facilities technician can do. Our emergency light testing guide covers the monthly and annual test routine; this article is about what to do when a test fails.

Safety first: emergency lights are connected to the mains. Isolate the supply before opening any fitting, and remember that a charged battery can still drive the LEDs and terminals inside.

How the test button works

A self-contained emergency light has a mains supply, a charger, a battery, a changeover circuit and an LED driver. The test button simulates a power failure: it disconnects the mains sense input so the changeover circuit switches the LEDs to battery. If any link in that chain is broken, the test fails.

That means “test button not working” can mean three different things:

  1. Nothing happens — the circuit never switches to battery, or the battery has nothing to give.
  2. The light comes on briefly and goes out — it switches, but the battery cannot sustain the load.
  3. The light was already off — a non-maintained light is normally dark; on a maintained light, the normal lamp may have failed.

Step 1: check the charge indicator

Most emergency lights have a small green LED showing that the battery is charging.

Indicator Likely meaning Next step
Off No mains at the charger Check the permanent live, fuse and wiring (Step 2)
Steady green Charging current flowing Check charge time (Step 3), then battery (Step 4)
Flashing or red (self-test models) Unit has detected a fault Read the fault code in the manual

Step 2: no charge indicator — check the supply

An emergency light must be connected to a permanent live, an unswitched supply from the same final circuit as the normal lighting. Common wiring faults:

  • Only a switched live connected. The battery charges only while the room lights are on, so it is often flat, and switching the room lights off makes a maintained unit go dark.
  • Permanent live and switched live swapped. Turning off the room lights triggers emergency mode and drains the battery.
  • Local fuse or test key switch open. Many installations have a key switch per circuit for testing; if it was left in the test position, the lights have been running on battery and are now flat.

Our emergency light installation guide shows the standard connections.

Step 3: charge indicator on — was it charged long enough?

New lights, and lights that have just done a full-duration test, need time. Our BG-XFYJ LED exit sign is specified with a charging time of up to 24 hours and at least 90 minutes of emergency operation. A sign installed in the morning and tested in the afternoon may run only for a short time, which looks like a fault but is not.

After a full-duration test, the building is at risk until the batteries recharge. That is why annual tests are scheduled at a time when the building can be left with reduced emergency cover, or done in alternate halves.

Step 4: test the battery

If the light was charged and still fails, the battery is the most common cause. Batteries in emergency lights typically last around four years, less in hot ceiling voids.

Signs of a worn battery:

  • The light comes on but goes out after a few minutes
  • The light is dim on battery
  • The battery is swollen, leaking or corroded at the terminals

Check the capacity against the need. Work out the energy the light needs for its rated duration:

Energy needed (Wh) = LED power on battery (W) × duration (h)

For a 3 W exit sign at 90 minutes that is 3 × 1.5 = 4.5 Wh delivered to the LEDs. Allowing about 80% conversion efficiency in the driver, the battery must still deliver about 5.6 Wh at the end of its life. A 3.6 V battery pack therefore needs at least about 1.6 Ah of remaining capacity, and more when it is new to allow for ageing. If a replacement battery is much smaller than the original, the light will fail its duration test even when new.

Check the plug. Batteries are often shipped disconnected to prevent discharge in transit. A battery that was never plugged in is a surprisingly common cause of a “dead” new light.

Replace like for like: same chemistry (NiCd, NiMH or LiFePO4), voltage and at least the same capacity. Chargers are designed for one chemistry; fitting a different one can damage the battery or fail to charge it.

Step 5: the test switch and electronics

If the supply and battery are good:

  • Test switch. Small push buttons can fail open, especially in damp or dusty areas. With the supply isolated, check continuity across the switch when pressed.
  • Changeover circuit. If disconnecting the mains supply (rather than pressing the button) makes the light work, the switch or its connection is the problem. If neither works, the changeover circuit or LED driver has failed, and replacing the whole fitting is usually more economical.
  • LED module. On a maintained light, if the normal lamp works but emergency mode does not, the emergency driver or battery is at fault; if neither works, check the LED module.

Quick fault-finding table

Symptom Most likely cause Fix
No charge light, no test No permanent live, fuse, test key left on Correct the supply
Charge light on, nothing on test, new unit Battery not connected or not charged Plug in battery, charge 24 h
Charge light on, light dies within minutes Battery worn out Replace battery
Lights go to emergency when room lights switched off Permanent and switched lives swapped Rewire
Works when mains removed, not with button Faulty test switch Replace switch or fitting
Nothing works, battery and supply good Failed driver or changeover board Replace fitting

Damp, hot and hazardous locations

  • Damp areas: corrosion on terminals and switches is the main cause of failures. Use fittings rated for the location; see our guide to wet location emergency lights.
  • Hot ceiling voids: high temperatures shorten battery life sharply. Mount the battery pack where it stays cool, or choose a fitting rated for the temperature.
  • Hazardous areas: do not open explosion-protected fittings in a live hazardous area. Our BG-FBYJ10A explosion-proof emergency light (Ex d IIC T4, 2 hours emergency operation) must be serviced by a competent person following the site’s permit procedure. See explosion-proof emergency exit lights for more.

Keep a record

Log every failed test, the cause found and the repair date. Codes such as BS 5266-1 in the UK and NFPA 101 in the USA require records of tests and repairs. A pattern of battery failures in one area usually points to heat or a charging fault, not to bad luck.

If several lights in a building fail at once, it may be time to replace them rather than repair. Our article on emergency light types explains maintained, non-maintained and self-test options, and self-test models report failures automatically so a stuck test button is no longer the only way to find a flat battery.

Sources

  1. BS 5266-1:2016 Emergency lighting — Code of practice
  2. NFPA 101 Life Safety Code, section 7.9 Emergency lighting
  3. BlueGreen OE — BG-XFYJ LED emergency exit sign specifications

Frequently asked questions

Why does my emergency light not come on when I press the test button?

Most often the battery is not charged, the battery plug is disconnected, or the light has no permanent (unswitched) live, so its battery never charges. Less often the test switch itself or the LED driver has failed. Check the charge indicator first.

How long should an emergency light charge before testing?

Follow the manufacturer's figure, commonly 24 hours for a full charge after installation or after a full-duration test. A short monthly test can be done once the charge indicator shows normal charging, but the annual full-duration test needs a fully charged battery.

Is there a problem if the charge light is on but the test fails?

The charge indicator only shows that charging current is flowing. A battery at the end of its life can accept current and still hold almost nothing. If the light dims or goes out early in a test, replace the battery.

Can I test an emergency light by switching off the light switch?

Usually not. The light switch controls the switched live for normal lighting; the emergency unit is fed from a separate permanent live. Switching off the wall switch should not trigger emergency mode in a correctly wired maintained or non-maintained unit.