Emergency Exit Light Covers and Guards: Wire Cages, Polycarbonate Shields and Damp-Proof Boxes Compared

Which cover or guard to put over an exit sign or emergency light in gyms, schools, car parks and damp areas, how to size it, and what a cover must not block, using our slim exit sign sizes.

Key points

  • Covers for exit signs and emergency lights come in three types: wire guards against balls and knocks, polycarbonate shields against vandalism, and sealed boxes against damp and dust.
  • Impact resistance is rated by IK code: IK08 withstands 5 joules, IK10 withstands 20 joules; sports halls and public areas usually ask for IK08 or higher.
  • Our slim BG-XFYJ exit signs measure 330 × 145 × 19 mm (3 W) and 330 × 149 × 22 mm (5 W), so a guard needs an inside size of at least about 370 × 190 mm with depth to spare.
  • A cover must not hide the legend, block the charge indicator or test button, or cut the light so much that the sign no longer meets its viewing distance.
  • A cover does not raise a fitting's IP rating by itself; for wet areas choose a fitting rated for them.

Exit signs and emergency lights sit at head height or above doors, in exactly the places where balls fly, trolleys knock and people with spare time look for something to break. A cover or guard protects them. The wrong cover, though, can hide the legend, block the test button or trap heat in the battery. This guide compares the main types and explains how to size one, using the real dimensions of our own exit signs.

Three kinds of cover

Type Protects against Typical places Effect on light
Wire guard (steel cage) Balls, knocks, falling objects Gyms, sports halls, warehouses, plant rooms Small; the wires cast thin shadows
Polycarbonate shield Vandalism, tampering, impacts Car parks, stairwells, schools, prisons, transit Small loss if clear and kept clean
Sealed box or enclosure Damp, dust, washdown Food plants, car washes, outdoor canopies Depends on design; check rating

Many buyers need the first two. The third is often better solved by choosing a different fitting.

Wire guards

A wire guard is a cage of steel wire, usually powder-coated, screwed to the wall or ceiling around the sign. It lets air move freely, so the battery and LEDs stay cool, and it hides almost nothing of the legend. It does not stop a determined vandal or protect from water.

Gyms are the classic case. A volleyball or basketball can hit a sign hard enough to crack its face or knock it off its bracket. Our guide to gym lighting covers guards for the main lighting too.

Polycarbonate shields

A clear polycarbonate (PC) shield fits over the sign as a box or a curved cover. It resists heavy blows and prevents people from pulling the sign apart or removing the battery. Choose a UV-stabilised PC so it stays clear, and keep it clean: a dirty shield can reduce visibility.

Make sure the shield has ventilation slots or a gap at the edges. A sealed PC box around a sign with a charging battery can run warm, which shortens battery life.

Damp and dust

A cover is not a substitute for an ingress protection rating. Our BG-XFYJ exit signs are IP40, intended for dry indoor areas. A wire guard adds nothing against water; a shield only deflects drips. For car washes, cold stores, outdoor canopies and food plants, choose a fitting rated IP65 or higher; our guide to wet location emergency lights explains the options.

Impact ratings: the IK code

IEC 62262 rates enclosures for impact resistance with an IK code:

IK code Impact energy Rough equivalent
IK06 1 J A 250 g mass dropped 40 cm
IK07 2 J A 500 g mass dropped 40 cm
IK08 5 J A 1.7 kg mass dropped 30 cm
IK09 10 J A 5 kg mass dropped 20 cm
IK10 20 J A 5 kg mass dropped 40 cm

Sports halls and public interiors usually ask for IK08 or better; car parks and areas prone to vandalism often ask for IK10. Ask the guard maker for the tested rating, not a material description.

Sizing a guard for our exit signs

Our LED exit sign BG-XFYJ is slim, which makes guarding easier:

Model Power Size Weight Emergency time
BG-XFYJ03A 3 W 330 × 145 × 19 mm 1.2 kg ≥ 90 min
BG-XFYJ05A 5 W 330 × 149 × 22 mm 1.4 kg ≥ 90 min

Allow about 20 mm of clearance on each side, so the guard does not touch the sign when struck and so air can move around it. That gives an inside size of at least about 370 × 190 mm. Depth should leave room for the sign plus its bracket and the same clearance in front; for a wall-mounted slim sign, 60–80 mm of inside depth is typical. For a ceiling-hung or double-sided sign, a guard must enclose both faces.

What a cover must never do

  1. Hide the legend. The running-man symbol and arrow must remain fully visible and legible at the sign’s viewing distance.
  2. Block indicators. The charge indicator light must stay visible so staff can see the battery is charging.
  3. Block testing. If the fitting has a test switch, it must stay reachable, or the guard must open easily. Monthly function tests and annual full-duration tests are standard practice; see emergency light testing.
  4. Trap heat. Fully sealed boxes without ventilation can overheat the battery.
  5. Change the colour. A tinted shield can alter the green that people recognise; use clear material.

Ordering signs with guards

Ordering the guard with the sign avoids mismatched sizes. Tell us:

  • The model and quantity of signs
  • Wall, ceiling or double-sided mounting
  • The area: gym, car park, stairwell, plant room
  • The IK rating your specification asks for

For help choosing the sign itself, see edge-lit exit signs and green vs red exit signs. Our commercial lighting range includes exit signs and emergency fittings for most buildings.

Sources

  1. IEC 62262 — Degrees of protection provided by enclosures against external mechanical impacts (IK code)
  2. ISO 7010 — Graphical symbols, safety signs (emergency exit signs)
  3. BlueGreen OE — LED exit sign BG-XFYJ specifications

Frequently asked questions

Can you put a cover over an exit sign?

Yes, if the cover keeps the legend fully visible and readable at its viewing distance, does not block indicators or the test switch, and does not trap heat. Clear polycarbonate or open wire guards are the usual choice.

What is a wire guard for an exit sign?

A steel wire cage fixed over the sign to protect it from balls and knocks. It is standard in gyms, sports halls and plant rooms.

What IK rating should an exit sign guard have?

IK08 (5 joules) is a common minimum for sports halls and public areas; IK10 (20 joules) is used where vandalism is likely, such as car parks and stairwells.

Does a cover make an exit sign waterproof?

Not on its own. An open guard adds no water protection, and a shield only deflects drips. For damp or outdoor areas, choose a sign or emergency light rated IP65 or higher.