Street Light Pole Wiring Diagram: From Feeder Pillar to Luminaire

A street light pole wiring diagram explained step by step: feeder cable, pole cut-out fuse, riser cable, photocell, surge protector and earth, plus a voltage-drop check for a 1 km road.

Key points

  • A street light pole has four wiring zones: the underground feeder, the cut-out (fuse) box at the base, the riser cable up the pole, and the luminaire with its photocell and surge protection.
  • Each pole taps the feeder through its own fuse, so one faulty light does not trip the whole street.
  • In our 1 km example, 29 poles of 100 W on one single-phase 16 mm² feeder lose about 6.5 % of the voltage; spreading them over three phases cuts that to about 1.1 %.
  • Every pole, and the luminaire, must be bonded to earth; a surge protector at the luminaire protects the LED driver from lightning and switching surges.
  • Our LDM30C street light accepts 185–264 V AC, which tolerates normal feeder voltage drop, but cable sizing should still follow the local voltage-drop limit.

When a contractor or a municipal engineer asks for a “street light pole wiring diagram”, they usually want two things: how the pieces connect inside one pole, and how many poles a feeder can carry before the voltage at the end of the street sags. This guide covers both, with a worked voltage-drop check for a 1 km road lit by our LDM30C luminaires.

The four wiring zones of one pole

Feeder pillar Pole base (handhole) Pole top
──────────── ──────────────────── ────────
L1 L2 L3 N PE ──┬──► Cut-out box Luminaire
(contactor / │ ├─ incoming feeder (loop in) ├─ photocell receptacle
timer / RCD) │ ├─ fuse on phase ├─ surge protector (SPD)
│ ├─ neutral link ├─ LED driver
│ ├─ earth terminal ── pole bond └─ LED module
│ └─ outgoing feeder (loop out)
│ │
│ riser cable 3 × 1.5–2.5 mm² ─────────►
└──► next pole

1. Feeder cable. An armoured cable runs underground from the feeder pillar (the street lighting cabinet) along the road. It loops in and out of each pole base, so the cable is continuous and each pole taps it.

2. Cut-out box at the base. Behind the handhole door sits a small box with:

  • Terminals for the incoming and outgoing feeder
  • A fuse (or small circuit breaker) on the phase feeding this pole only
  • A neutral link
  • The earth terminal, bonded to the pole and to the feeder’s protective conductor

3. Riser cable. A 3-core cable (phase, neutral, earth), usually 1.5 or 2.5 mm², runs from the cut-out up inside the pole and along the arm to the luminaire.

4. Luminaire. Inside the housing, the supply passes through the photocell (if fitted to the luminaire), a surge protective device and the LED driver.

Inside the luminaire

Part Connection Purpose
Photocell receptacle (NEMA 3, 5 or 7-pin, or Zhaga) Switches the live to the driver; extra pins for dimming Dusk-to-dawn switching, smart control
Surge protective device Across live, neutral and earth, before the driver Diverts surges from lightning and switching
LED driver Mains in, DC out to the LED module Constant current; often 0–10 V or DALI dimming input
Earth To the housing Protection against indirect contact

Our guide to photocells for outdoor lights explains how the receptacle pins are used, and LED streetlight components covers the driver, optics and housing.

Switching: per-luminaire or per-circuit

  • Per-luminaire photocell: each light switches itself. Simple and resilient; one failed photocell affects one light.
  • Per-circuit contactor: a photocell or astronomical timer in the feeder pillar switches a contactor, energising the whole circuit at dusk. The poles then carry no switching devices. This is common on older networks and wherever a central management system controls the street.

Either way the pole wiring is the same; only the position of the switching device changes.

Worked example: voltage drop on a 1 km road

Suppose a 10 m wide road with lighting class M4 and 10 m poles. Our pole height and spacing calculator with a 100 W LDM30C street light at 110 lm/W gives:

  • Single-sided layout, utilisation factor 0.51
  • Spacing 35 m (limited by the 3.5 × height rule), average about 12.7 lux against 11 lux required
  • 29 poles per km, 2.9 kW per km

Open the example and enter your own road.

Current. 2,900 W ÷ (230 V × 0.97 power factor) ≈ 13.0 A in total.

Option A: all 29 poles on one phase. With a 16 mm² copper feeder (about 1.15 Ω per km per conductor), the loop resistance of phase and neutral is 2.3 Ω per km. For a load spread evenly along the run, the drop at the far end is about half of what it would be if all the load sat at the end:

13.0 A × 2.3 Ω × 0.5 ≈ 15 V, or about 6.5 % of 230 V.

Option B: poles connected to L1, L2 and L3 in turn. Each phase carries a third of the current, about 4.3 A, and with a balanced load the neutral carries almost nothing:

4.3 A × 1.15 Ω × 0.5 ≈ 2.5 V, or about 1.1 %.

Our LDM30C accepts 185–264 V AC, so even Option A keeps the last luminaire running. But most codes limit voltage drop on lighting circuits (IEC 60364-5-52 suggests 3 % for installations fed from the public supply and 6 % for private supplies, as a guide), and Option B meets either with margin. Rotating the phases also balances the supply transformer.

Earthing and protection

  • Earth every pole to the feeder’s protective conductor, and add an earth rod at the feeder pillar and at intervals if the local code or soil conditions require.
  • Protect the circuit at the feeder pillar with a breaker sized for the feeder, plus an RCD where the earthing system calls for one (IEC 60364-7-714 covers external lighting).
  • Protect each pole with its own fuse, rated for the riser cable and the luminaire’s inrush current. LED drivers have short inrush peaks, so check the driver datasheet before choosing a small breaker.
  • Fit surge protection at the luminaire (and often at the pillar), especially on long rural circuits and in lightning-prone regions.

Common wiring faults

Symptom Likely cause
One light out, rest working Blown pole fuse, failed driver or photocell
Every third light out One phase lost at the feeder pillar
Lights at the end of the street dim or flicker Undersized feeder, loose neutral, high voltage drop
Lights on all day Failed photocell or contactor stuck closed
RCD trips in wet weather Water in a cut-out box or a damaged riser cable

Our article on street light cycling on and off covers photocell faults, and street light foundation design shows how the cable duct enters the pole base. For tall masts with many floodlights on one pole, see our high mast lighting wiring diagram.

What to send us

Send the road width, length, pole height, supply voltage and whether you plan per-luminaire photocells or central control. We will return the spacing, the luminaire wattage and a load table per phase that your electrical designer can use to size the feeder.

Sources

  1. IEC 60364-5-52 — Selection and erection of electrical equipment: wiring systems
  2. IEC 60364-7-714 — Requirements for special installations: external lighting installations
  3. ANSI C136.41 — Dimming receptacle for roadway luminaires

Frequently asked questions

How is a street light pole wired?

An underground feeder cable loops into a cut-out box in the pole base. A fuse in that box feeds a smaller riser cable up the pole to the luminaire. The luminaire contains the LED driver, a surge protector and usually a photocell receptacle. The pole and luminaire are earthed.

What size cable goes up a street light pole?

Commonly a 3-core 1.5 mm² or 2.5 mm² cable for a single luminaire, because the riser carries only one light's current. The feeder in the ground is much larger, often 10–35 mm², sized for the whole circuit and its voltage drop.

Do street lights run on single phase or three phase?

Each luminaire is single-phase (phase and neutral), but long circuits are usually fed from a three-phase supply, with poles connected to L1, L2 and L3 in turn. That balances the load and keeps voltage drop low.

Where does the photocell go in the wiring?

On most modern street lights the photocell plugs into a NEMA or Zhaga receptacle on top of the luminaire and switches the driver's live supply. Older systems switch a whole circuit from a contactor in the feeder pillar.

Why does each pole have a fuse?

To isolate a fault at one pole. If a luminaire or riser cable fails, its own fuse blows and the rest of the street stays lit. It also gives a safe isolation point for maintenance.