Street Light Design Standards: Which One Applies and How It Changes the Design

A buyer's map of street lighting design standards: EN 13201, IES RP-8, CIE 115, BS 5489, AS/NZS 1158, IS 1944 and CJJ 45, what each sets, and how the class changes wattage and spacing.

Key points

  • Most national street lighting standards descend from CIE 115; Europe uses EN 13201, North America IES RP-8, Australia AS/NZS 1158, India IS 1944 and China CJJ 45.
  • Every standard does the same three things: picks a lighting class for the road, sets a quantity (luminance or illuminance) with a uniformity, and limits glare.
  • In our calculator, the same 7 m road on 8 m poles needs about 70 W per light for class M3 at 24 m spacing, but only 35 W for M5 or P3 at 28 m; the class decides the wattage more than the pole does.
  • Tenders should state which standard and class apply; a light that meets one standard's class does not automatically meet another's.

When a tender says “design to the relevant standard”, the first question is which one. Street lighting standards differ by country, and each uses its own class names and quantities. The good news is that they share a common structure, so once you know one you can read the others. This guide maps the main standards, explains what each sets, and shows with our calculator how much the chosen class changes the wattage and spacing.

The family tree

Most road lighting standards trace back to CIE 115 from the International Commission on Illumination. National bodies adapt it to their roads and traffic:

Standard Where it applies Class names Main quantity for traffic routes
CIE 115 International reference M, C, P Luminance (cd/m²) or illuminance (lux)
EN 13201 (parts 1–5) EU and many tenders in Africa, the Middle East and Asia M, C, P, plus HS, SC, EV Luminance for M classes, illuminance for C and P
BS 5489-1 United Kingdom (applies EN 13201 classes) M, C, P As EN 13201
IES RP-8 USA, Canada and many Latin American projects By road type and pedestrian conflict Luminance or illuminance, plus veiling luminance ratio
AS/NZS 1158 Australia and New Zealand V (vehicular), P (pedestrian) Luminance for V, illuminance for P
IS 1944 India Groups A to E by road type Illuminance with uniformity
CJJ 45 China (urban roads) Express, main, secondary, branch roads Luminance and illuminance

If you are tendering in Europe or for an international bank-funded project, EN 13201 is the usual reference. Our EN 13201 road lighting classes article lists the class values and the parameter method for choosing one.

What every standard sets

Under the different names, each standard fixes the same things:

  1. A lighting class for the road. Chosen from speed, traffic volume, mix of users, junctions and ambient brightness. Higher speed and more conflict mean a higher class.
  2. A quantity and a uniformity. Traffic routes are usually designed to road surface luminance (what the driver sees reflected off the road); pedestrian areas and conflict zones to illuminance on the ground. Uniformity limits the dark patches between poles.
  3. A glare limit. EN 13201 uses threshold increment (TI); RP-8 uses the veiling luminance ratio. Both stop drivers being dazzled by the lights.
  4. Surround lighting. Some light must fall beyond the kerb so that pedestrians and obstacles at the edge are visible (edge illuminance ratio in EN 13201).

The design then has to show, by photometric calculation with the real luminaire file, that every value is met with a maintenance factor applied.

How much the class changes the design

To show the effect of the class alone, we ran one road through our pole height and spacing calculator: a 7 m two-lane road, 8 m poles on one side, 60 W lights at 110 lm/W and a maintenance factor of 0.8. The calculator works in average illuminance, so it uses illuminance equivalents for the M classes; it is a first estimate, not a substitute for a luminance calculation.

Class Target in calculator Spacing Average achieved Lights per km Power that just meets the class
M3 15 lux 24 m 15.1 lux 42 70 W
M4 11 lux 28 m 12.9 lux 36 51 W
M5 7.5 lux 28 m 12.9 lux 36 35 W
M6 4.5 lux 28 m 12.9 lux 36 21 W
P2 10 lux 28 m 12.9 lux 36 46 W
P3 7.5 lux 28 m 12.9 lux 36 35 W
P4 5 lux 28 m 12.9 lux 36 23 W

(open the M3 example · open the P3 example)

At 8 m, spacing is capped at 3.5 times the pole height (28 m) to keep uniformity reasonable, so for every class below M3 the spacing stops at 28 m and the real choice is the wattage. The last column is the number to watch: from M3 to P4 the required power falls from 70 W to 23 W on the same poles. Choosing the class correctly is worth more than any product decision.

Reading a standard into a specification

When you write or answer a specification, make sure it states:

  • The standard and edition, for example “EN 13201-2:2015”.
  • The class for each road section, including junctions and crossings, which often need a higher class or C class.
  • The maintenance factor and the cleaning interval it assumes.
  • The surface reflection table (R-table) for luminance designs, such as R3 for typical asphalt.
  • The calculation grid and observer positions, which EN 13201-3 defines.
  • Required outputs: average, uniformity, TI or veiling luminance ratio, and edge ratio.

A light that meets M3 under EN 13201 will not automatically meet the equivalent RP-8 criteria, because the quantities, grids and glare metrics differ. When a project mixes references, ask which one governs.

What the standards do not cover

Design standards set how much light a road needs. They do not certify the luminaire. Product safety, ingress protection, surge protection and photometric testing fall under product standards such as IEC 60598-2-3 for road luminaires and LM-79 or EN 13032 for measurements. In tenders, ask for both: a design report to the road standard and test reports for the product.

For our own street lights, the LDM30C modular LED street light is rated above 110 lm/W with an IP67 body, and the BGLDM30C version (60–300 W) holds a CQC product certificate, CQC19010221751. We supply IES files for design calculations; our IES files and photometric data article explains how designers use them.

Common mistakes

  • Designing to lux when the standard asks for luminance. M classes and RP-8 traffic routes are judged on luminance, which depends on the road surface and viewing angle.
  • One class for the whole scheme. Junctions, roundabouts and pedestrian crossings usually need more light than the road between them.
  • Ignoring the maintenance factor. A design that just meets the class with new lamps falls below it within a few years.
  • Skipping the glare check. A high-output light on a low pole can meet the average and fail TI.

Our street light pole distance calculation article walks through the spacing method step by step.

What to send us

Send the standard and class (or the road type, speed and traffic), road width and pole height, and any existing layout. We will reply with a first estimate from our calculator, the light we would propose and the IES file for your designer’s full calculation.

Sources

  1. CIE 115:2010 — Lighting of roads for motor and pedestrian traffic
  2. EN 13201-2 — Road lighting, performance requirements
  3. IES RP-8 — Recommended practice for design and maintenance of roadway lighting
  4. AS/NZS 1158 — Lighting for roads and public spaces

Frequently asked questions

What is the international standard for street lighting?

CIE 115, published by the International Commission on Illumination, is the reference most national standards are based on. Europe's EN 13201 follows its structure closely; other countries adapt it.

Which street lighting standard is used in the USA?

IES RP-8, the Illuminating Engineering Society's recommended practice for roadway lighting, together with local DOT or city specifications.

Do street lights have to meet a standard?

Public roads usually do, through the road authority's specification. Private estates and industrial roads often adopt the same standard voluntarily so that lighting is defensible after an accident.

What does a design standard not cover?

Product safety and quality. Electrical safety, ingress protection and photometric testing are covered by product standards such as IEC 60598, while the design standard sets how much light the road needs.

Products in this guide

Have a project?

Ask our engineers

Send us your site details and we will size the system and quote it.

We reply by email within one working day (China time, GMT+8). Your details are only used to answer this inquiry. Prefer chat? Message us on WhatsApp. Have more detail to give? Use the full form.