Parking Lot Lighting Design: Light Levels, Pole Layout and a 100 × 60 m Worked Example
Parking lot lighting design step by step: 5, 10 and 20 lux targets, pole height and spacing rules, distribution types, and a 100 × 60 m lot with 8 poles.
Key points
- Design to an average and a uniformity: EN 12464-2 asks for 5, 10 or 20 lux by traffic level, each with a minimum of one quarter of the average.
- Pole height sets the layout: space poles no more than about three to four times their height apart, and place rows no more than about twice the height from the area they light.
- A 100 × 60 m lot at 10 lux needs about 150,000 lumens at the fixtures, which is 14 fixtures of 100 W or 10 of 150 W at 110 lm/W.
- Laid out for uniformity, the same lot uses 8 twin-arm poles of 10 m with 16 fixtures of 100 W, giving about 12 lux for 1.6 kW.
- Put poles in the islands between facing rows of bays, so that one pole lights two rows and cars cannot hit it.
A parking lot is a simple space to light badly. A few powerful floodlights on a building wall will make it bright near the wall and dark at the far end, with glare for every driver who looks towards them. Good parking lot lighting design does the opposite: moderate light, evenly spread, from above. This guide walks through the design steps and applies them to a 100 × 60 m lot.
Step 1: choose the light level
| Use | EN 12464-2 average | Uniformity (minimum ÷ average) |
|---|---|---|
| Light traffic: shops, schools, housing, churches | 5 lux | 0.25 |
| Medium traffic: offices, supermarkets, plants, sports complexes | 10 lux | 0.25 |
| Heavy traffic: shopping centres, stadiums, large multi-purpose venues | 20 lux | 0.25 |
North American practice is written as a minimum, not an average: 0.2 foot-candles (about 2 lux) at the darkest point for basic use and 0.5 foot-candles (about 5 lux) for enhanced security, with limits on the ratio of maximum to minimum.
Both approaches make the same point. The darkest spot matters as much as the average, because that is where a pedestrian is not seen and where people do not feel safe.
Step 2: estimate the lumens
Lumens needed = area × target lux ÷ (utilisation factor × maintenance factor)
For parking lots, a utilisation factor of 0.5 and a maintenance factor of 0.8 are reasonable first values. For a 100 × 60 m lot (6,000 m²):
| Target | Lumens needed | 100 W fixtures | 150 W fixtures | 200 W fixtures |
|---|---|---|---|---|
| 5 lux | 75,000 | 7 | 5 | 4 |
| 10 lux | 150,000 | 14 | 10 | 7 |
| 20 lux | 300,000 | 28 | 19 | 14 |
The fixture counts use 110 lm/W, the figure for our modular LED street light LDM30C, which is made from 30 W to 350 W with a 140° × 80° road distribution and IP67 protection.
This step gives a minimum. It does not yet say whether the light will be even.
Step 3: choose the pole height
| Lot size | Typical pole height | Typical fixture |
|---|---|---|
| Small, up to about 30 m across | 6–8 m | 50–100 W |
| Medium | 8–10 m | 100–150 W |
| Large, open | 10–12 m | 150–250 W |
| Very large | 15 m and above, or high masts | Multiple floodlights |
Height buys uniformity. A fixture’s useful throw is proportional to its height, so taller poles can stand further apart. The limits are planning rules, the wind load on the pole and access for maintenance. See parking lot light poles for the pole itself.
Step 4: lay out the poles
Three spacing rules give a good first layout:
- Along a row: poles no more than about three to four times the mounting height apart.
- Across: a fixture lights well out to about twice its height in front of it.
- Edges: the first pole no more than about one to one and a half times its height from the end of the lot.
And two placement rules:
- Use the islands. A pole in the strip between two facing rows of bays, with a twin arm, lights both rows and both adjoining aisles. It is also protected from cars.
- Light inward at the perimeter. Poles on the boundary carry one fixture facing in, with a shield at the back if there are neighbours.
Worked example: 100 × 60 m at 10 lux
The lot is 100 m long and 60 m wide, used by a supermarket: medium traffic, 10 lux. Step 2 gave 150,000 lumens: 14 fixtures of 100 W or 10 of 150 W.
Layout. Two rows of poles run along the length, in parking islands 15 m in from each long edge, so the rows are 30 m apart. Each row has four twin-arm poles of 10 m.
| Check | Value | Rule |
|---|---|---|
| Spacing along the row | 25 m, 2.5 × height | Under 3–4 × height: passes |
| Distance from row to lot edge | 15 m, 1.5 × height | Under 2 × height: passes |
| Distance from row to the centre line | 15 m, 1.5 × height | Under 2 × height: passes |
| First pole to end of lot | 12.5 m, 1.25 × height | Under 1.5 × height: passes |
Fixtures. Eight poles with twin arms carry 16 fixtures. With 100 W fixtures at 110 lm/W:
| Quantity | Value |
|---|---|
| Total lumens | 176,000 |
| Calculated average (× 0.5 × 0.8 ÷ 6,000 m²) | 11.7 lux |
| Connected load | 1.6 kW |
| Power density | 0.27 W/m² |
So the layout needs 16 fixtures where the lumen count alone asked for 14. The two extra are the price of uniformity, and that is typical: the geometry of the lot, not the lumen total, sets the number of poles.
Alternative. Six poles of 12 m with twin 150 W fixtures (12 fixtures, 198,000 lumens, 13.2 lux, 1.8 kW) also passes the spacing rules, with poles 33 m apart. Fewer foundations, taller poles, slightly more energy. Which is cheaper depends on local foundation and pole costs.
For 20 lux, keep the same eight poles and use 200 W fixtures: 352,000 lumens and 23.5 lux.
These are first estimates by the lumen method. The uniformity of 0.25 must be confirmed with photometric software and the real distribution of the fixture.
Step 5: choose the light distribution
| Position | Distribution | Why |
|---|---|---|
| Perimeter, lighting inward | Forward throw (Type IV) or asymmetric | Pushes light into the lot, little behind the pole |
| Island between bays, twin arm | Wide road distribution (Type III) | Each fixture covers its side of the island |
| Centre of a large open area | Symmetric (Type V) | Light in all directions |
| Along an access road | Road distribution (Type II or III) | Long and narrow |
Mount the fixtures flat, with no upward tilt. Tilting a fixture to “reach further” sends light into drivers’ eyes and into the sky.
Step 6: controls and colour
- Colour temperature. 4,000 K is the common choice; 3,000 K near housing.
- Photocell or astronomical timer for dusk-to-dawn switching.
- Dimming after closing. Many lots dim to 30–50% once the business closes, and return to full output on motion.
- Surge protection. Poles in open lots are exposed to lightning-induced surges.
For lots with no supply nearby, see solar parking lot lighting.
Entrances, walkways and pay stations
Design these separately, above the general level:
- entrances and exits, where cars meet the road and eyes must adapt;
- pedestrian routes to the building;
- pay stations, trolley bays and accessible parking bays.
A common approach is to give these areas about twice the general level, with an extra pole or a higher wattage at those points.
Common mistakes
| Mistake | Result |
|---|---|
| Floodlights on the building wall only | Glare, and a dark far side |
| Designing to the average alone | Dark patches between poles |
| Poles too short for the spacing | Bright pools and dark gaps |
| Tilted fixtures | Glare and light trespass |
| Poles in the bays instead of the islands | Collision damage |
Next steps
For the installation work itself, from trenching to commissioning, see parking lot lighting installation. For fixture choice, see LED parking lot lights.
Send us a plan of the lot with dimensions, the use, any height limit and the supply voltage. We return a pole layout, the fixture schedule and a calculated lux grid.
Sources
Frequently asked questions
How many lux should a parking lot have?
EN 12464-2 gives 5 lux for light traffic such as shops and housing, 10 lux for medium traffic such as offices and supermarkets, and 20 lux for heavy traffic such as shopping centres and stadium car parks. US practice sets a minimum of 0.2 foot-candles, or 0.5 where security is a concern.
How far apart should parking lot light poles be?
As a starting rule, three to four times the mounting height: 30–40 m for 10 m poles. Closer spacing gives better uniformity. The rows of poles should be no more than about four times the height apart.
How tall should parking lot light poles be?
6–8 m for small lots, 8–10 m for medium ones and 10–12 m for large lots. Taller poles mean fewer of them and better uniformity, but check local limits on pole height and light spill.
How do I calculate how many parking lot lights I need?
Multiply the area by the target lux and divide by 0.4, which combines a utilisation factor of 0.5 and a maintenance factor of 0.8. That gives the lumens needed. Divide by the lumens of one fixture, then check the count against the pole spacing rules.