Explosion-Proof Junction Boxes for Lighting Circuits: Ex d or Ex e?
How to choose an explosion-proof junction box for hazardous-area lighting: Ex d vs Ex e, glands, terminal ratings, and a worked circuit for eight 100 W floodlights with voltage drop.
Key points
- An Ex e (increased safety) junction box is the usual choice for lighting circuits: it holds only terminals, is lighter and is easier to inspect than an Ex d box.
- Choose Ex d when the box must contain parts that spark in normal use, such as switches or fuses, or when the site standard asks for it.
- Glands must match the box: Ex e glands on Ex e boxes, Ex d glands (with barrier glands where IEC 60079-14 requires) on Ex d boxes.
- A run of eight 100 W BAD8599 floodlights draws about 3.8 A at 220 V; on 2.5 mm² cable over 120 m the worst-case voltage drop is about 3 %.
Every light in a hazardous area is wired back to a circuit through one or more junction boxes. The box is often treated as a minor item, yet it sits in the same zone as the light and must meet the same rules. This guide covers how to choose between the two common types, what to check on glands and terminals, and how to size a typical lighting circuit.
Two protection types
| Ex e (increased safety) | Ex d (flameproof) | |
|---|---|---|
| Principle | Prevents sparks and hot spots by design: certified terminals, creepage distances, sealed IP54+ enclosure | Contains an internal explosion and cools escaping gases through flame paths |
| What it may contain | Terminals and cable only | Terminals, switches, fuses, relays |
| Typical material | Glass-reinforced polyester or stainless steel | Cast aluminium or stainless steel |
| Weight | Light | Heavy |
| Inspection | Open, check terminals, close | Must not damage flame paths; bolts all in |
| Zone | 1 and 2 (eb); 2 only (ec) | 1 and 2 (db) |
For a plain lighting circuit, where the box only joins cables, Ex e is the normal choice. It is cheaper, lighter and quicker to inspect. Our Ex e increased safety guide explains how the protection works.
Choose Ex d when the box must hold a local isolator, fuse or contactor, or when a site standard asks for flameproof throughout. Our explosion-proof vs flameproof article explains the terms.
How our BED series uses both
The BED series shows the same logic inside one luminaire. Its marking, Ex db eb mb IIC T4 Gb, means:
- db: the LED chamber is flameproof;
- eb: the terminal compartment is increased safety;
- mb: the driver is encapsulated.
The installer terminates the supply in the Ex e compartment and never opens the flameproof chamber. That is the same reason Ex e boxes are preferred on circuits: wiring work happens in a compartment that is quick to open and close correctly. The BED is covered by our certificate ZJEx23.0914 under GB 3836.
Checks before you buy a box
- Marking matches the zone and gas. For a IIC area the box must be IIC; for Zone 21/22 dust, it needs a dust marking too.
- Temperature class. Terminal boxes run cool, but the certificate states the maximum current per terminal size for the declared T class. Stay within it.
- Terminal count and size. Count line, neutral and earth for the incoming and outgoing cables, plus spares. Do not double up conductors unless the terminal is certified for two.
- Entries. Number, thread (M20, M25, NPT) and position. Unused entries must be closed with certified stopping plugs of the same protection type.
- Ingress protection. IP66 is common outdoors; check the gland and plug ratings too.
- Material. Stainless or GRP near the sea or in chemical plants; see our WF1 vs WF2 guide.
Glands
The gland belongs to the protection concept of the enclosure it enters:
- Ex e box: Ex e glands that keep the IP rating and grip the cable.
- Ex d box: Ex d glands. IEC 60079-14 decides when a barrier (compound-filled) gland is required instead of a standard compression gland; this depends on the zone, gas group, the internal volume and whether the box contains a source of ignition.
- Armoured cable: the gland must also terminate the armour and provide earth continuity.
In North American Division 1 practice with conduit, seals are fitted close to enclosures that contain arcing parts. Follow the code that applies to the site.
Worked circuit: a tank farm pump bay
A 24 × 12 m covered pump bay in a tank farm, Zone 1 IIB, fittings at 6 m and a 100 lux target. With 100 W BAD8599 floodlights (Ex d IIC T6 Gb, at least 120 lm/W) and a wide beam, our high bay lighting calculator gives 8 fittings in a 4 × 2 grid, about 153 lux (open the example).
The circuit, at 220 V and the BAD8599’s rated power factor of 0.95:
- current per light: 100 ÷ (220 × 0.95) = 0.48 A;
- eight lights: 3.83 A, comfortable on a 10 A circuit;
- cable: 2.5 mm² copper, maximum 7.41 Ω/km per IEC 60228;
- feed length 120 m to the far end, 240 m loop: 1.78 Ω;
- worst case, all load at the end: 3.83 × 1.78 = 6.8 V, or 3.1 %.
The real drop is lower because the lights are spread along the run, and the BAD8599 accepts 90–265 V, so 3 % has no effect on light output. A daisy chain through each light’s terminal box would avoid most junction boxes; where the route branches, one Ex e box per branch point is typical.
The calculator also shows that 65 W per fitting would meet 100 lux with the same grid; the 100 W choice leaves margin for dirt on the glass in a tank farm.
Installation points
- Torque terminal screws to the value on the certificate.
- Keep the earth conductor continuous through every box.
- Label boxes with circuit numbers; inspectors check this.
- Record each box in the hazardous-area equipment register with its certificate number.
Our explosion-proof light installation guide covers mounting and commissioning of the lights themselves.
What to send us
Zone, gas group and temperature class, the room or yard dimensions, mounting height and the circuit voltage. We will return a fitting count, the circuit current from our calculation, and the certificate for the light we propose.
Sources
Frequently asked questions
What is an Ex JB?
Ex JB is shorthand for an explosion-protected junction box: an enclosure for joining cables in a hazardous area, certified to a protection type such as Ex e (increased safety) or Ex d (flameproof).
Can I use an Ex e junction box in Zone 1?
Yes. Ex eb boxes are equipment protection level Gb and are permitted in Zone 1 and Zone 2. They must contain only certified terminals and no sparking parts.
Do I need a barrier gland on an Ex d junction box?
IEC 60079-14 sets the rules. Barrier (compound) glands are needed in some cases, for example certain Zone 1 IIC installations or where the enclosure contains an internal source of ignition. Follow the gland selection chart in the standard and the box certificate.
How many lights can I put on one circuit?
It depends on current, voltage drop and inrush. For eight 100 W LED floodlights at 220 V the steady current is under 4 A, well within a 10 A or 16 A circuit, but check the driver inrush against the breaker curve.