Get a quote

Dimmable LED Tube Lights: Which Tube Types Dim, and How to Wire Them

Which LED tube types can be dimmed, how 0–10 V, DALI and TRIAC dimming work with tubes, what goes wrong, and a 200-fitting savings example from our retrofit calculator.

Key points

  • Most LED tubes are not dimmable; dimming depends on the tube type and on a driver or ballast made for it.
  • External-driver (Type C) tubes are the most reliable way to dim, because the dimmable 0–10 V or DALI driver sits in the fitting, not in the tube.
  • In our retrofit calculator, replacing 200 twin 36 W fluorescent fittings with twin 18 W LED tubes saves about 28,500 kWh a year (55 %) at 11 hours a day, 300 days a year.
  • Dimming to 50 % for five of those eleven hours saves roughly another 5,400 kWh, but only if the tubes, drivers and controls are matched.

Swapping fluorescent tubes for LED is one of the quickest energy savings a building can make. Adding dimming should save more, but this is where many retrofits go wrong: tubes flicker at low levels, buzz on wall dimmers or simply refuse to dim. The reason is that “LED tube” covers several different products, and only some of them can be dimmed. This guide explains which, how they are wired and controlled, and what dimming adds to the savings. For the general conversion steps, see LED fluorescent tube replacement.

Why most LED tubes do not dim

A fluorescent tube was controlled by its ballast. An LED tube has a driver, either inside the tube or in the fitting, that turns mains power into the steady current the LEDs need. A driver only dims if it was designed to read a dimming signal. Most tubes sold for simple replacement are built to run at one level, as cheaply as possible.

Feeding such a tube through a dimmer does not reduce its output smoothly. The internal driver fights the chopped supply, which causes flicker, buzzing, early failure and sometimes overheating of the dimmer.

The tube types and dimming

Type How it is powered Dimming
A — ballast-compatible Runs on the existing fluorescent ballast Only on dimming ballasts the tube maker lists
B — direct wire Mains wired straight to the tube; ballast removed Only tubes with a built-in dimmable driver, usually TRIAC
C — external driver Low-voltage feed from a separate driver in the fitting Easy: choose a 0–10 V or DALI dimmable driver
A+B hybrid Works on a ballast or direct wire As A or B, depending on how it is installed

Type C is the most dependable route. The tube is just LEDs and a connector; all the electronics, including dimming, sit in a driver that can be chosen for the control system and replaced on its own.

Type A dimming relies on the old ballast, which also means the old ballast stays in service and will eventually fail.

Type B dimming exists but the choice is narrow. Most Type B tubes, including standard tubes like our BG-RG, are non-dimming.

The control signals

0–10 V

Two extra low-voltage control wires (purple and grey in many regions) run from a dimmer or controller to each driver. The driver reads the voltage: 10 V full output, around 1 V minimum. It is simple and widely used in offices and warehouses. The control wiring must be installed, which is easy in new work and harder in an existing ceiling.

DALI

DALI is a digital two-wire bus defined in IEC 62386. Each driver has an address, so lights can be grouped, scheduled and monitored from software without rewiring. It costs more per driver but suits larger buildings and sensor-based control.

TRIAC (phase-cut)

A wall dimmer cuts part of each mains cycle. No extra wires are needed, which is why it is common in homes and small shops. It works only with tubes and drivers sold as phase-cut dimmable, and the dimmer and tube should be on the maker’s compatibility list.

A worked savings example

Take a building with 200 twin-tube fittings (2 × 36 W fluorescent, with about 10 % ballast loss), lit 11 hours a day, 300 days a year, at $0.15 per kWh. We replace them with 2 × 18 W LED tubes, the size our product data gives as the 36 W replacement (about 1,620 lumens each). Our LED retrofit savings calculator gives (open the example):

  • old system: 79.2 W per fitting, 52,272 kWh a year;
  • LED: 36 W per fitting, 23,760 kWh a year;
  • saving 28,512 kWh (55 %), about $4,277 in energy plus $800 in maintenance a year;
  • payback about 9.5 months, with assumed costs of $12 for the tubes and $8 labour per fitting. Replace those with your own quote.

What dimming adds

Suppose the building can run at 50 % for five of the eleven hours (early morning, evening, or areas near windows). LED drivers draw a little more than half power at half light, but as a first estimate:

23,760 kWh × 5/11 × 50 % ≈ 5,400 kWh a year, about $810.

That is worthwhile, but it is a fifth of the LED’s energy, not a second retrofit’s worth. Dimming pays best when the hardware cost is small, for example when new fittings are being installed anyway, or when sensors and daylight control can cut many more hours.

Common problems with dimmed tubes

  • Flicker at low levels. Many drivers become unstable below 10–20 %. Set a minimum level in the controller.
  • Mixed tube brands on one circuit. Different drivers respond differently; one fitting will look brighter than its neighbour.
  • Pop-on. Some drivers cannot start at a low level and jump to full output first. Check this if lights switch on with sensors.
  • Unlisted combinations. A tube, ballast and dimmer that are each fine can still fail together. Use tested combinations.

When to choose new fittings instead

If dimming is a firm requirement, replacing old fittings with new LED fittings that have a dimmable driver is often simpler than converting tubes. Linear battens, troffers and panels with 0–10 V or DALI drivers avoid the compatibility questions completely. See LED tube and strip lights, LED troffer lights and recessed LED linear lights.

Safety and listings

Converting a fluorescent fitting to LED changes the product. In North America, retrofit kits are covered by UL 1598C. Mark converted fittings so that the next electrician does not fit a fluorescent tube into a direct-wired socket. Our LED retrofit kits guide covers this.

What to send us

The number and type of fittings, current tubes and ballasts, the control system you want, and operating hours. We will run the savings in our calculator and say plainly whether a tube retrofit or new fittings will give reliable dimming.

Sources

  1. UL 1598C — Light-emitting diode (LED) retrofit luminaire conversion kits
  2. IEC 62386 — Digital addressable lighting interface (DALI)
  3. IEC 60929 Annex E — 0–10 V (1–10 V) control interface for electronic ballasts
  4. BlueGreen OE — BG-RG LED T8 tube

Frequently asked questions

Are LED tube lights dimmable?

Only some. Standard ballast-bypass tubes on a wall dimmer will flicker, buzz or fail. Dimming needs a tube made for it, or an external-driver tube system with a dimmable driver.

Can I dim LED tubes with a normal wall dimmer?

Only tubes sold as TRIAC or phase-cut dimmable, and only with a dimmer the maker lists as compatible. Commercial sites usually use 0–10 V or DALI instead.

Do Type A (plug-and-play) tubes dim on a dimming ballast?

Some do, but only with the specific dimming ballasts the tube maker has tested. Check the compatibility list; an unlisted ballast may give a narrow dimming range or flicker.

How much energy does dimming LED tubes save?

Roughly in proportion to the dimmed hours and level. In our example, dimming to 50 % for five of eleven daily hours saves about a fifth of the LED energy.

Are your BG-RG tubes dimmable?

The published BG-RG range consists of standard, non-dimming tubes. If you need dimming, tell us the control system (0–10 V, DALI or TRIAC) and we will say whether we can supply a matching solution.

Products in this guide

Have a project?

Ask our engineers

Send us your site details and we will size the system and quote it.

We reply by email within one working day (China time, GMT+8). Your details are only used to answer this inquiry. Prefer chat? Message us on WhatsApp. Have more detail to give? Use the full form.

Related guides