High Mast Lighting Coverage Area: How Much Ground One Mast Lights at 20, 25, 30 and 35 m

How much area one high mast covers: tables for 20, 25, 30 and 35 m masts at 10, 20 and 50 lux, the radius-to-height rule, mast spacing and uniformity limits.

Key points

  • Coverage depends on the lux level you need: a 30 m mast with ten 600 W floodlights covers about 31,000 m² at 10 lux but only about 6,200 m² at 50 lux.
  • As a first estimate, one mast lights a circle with a radius of about three times its height at 10 lux and about twice its height at 20 lux.
  • Height sets how far light can be thrown evenly; wattage sets how bright it is. More watts on a short mast do not widen the coverage.
  • Masts are usually spaced three to four times their height apart so that the circles overlap.
  • Stacked goods, containers and buildings cast shadows, so real yards need light from at least two directions.

“How much area will one mast cover?” is the first question on almost every high mast enquiry, and it has no single answer, because coverage is not a property of the mast. It depends on three things: how high the floodlights are, how many lumens they produce, and how many lux the area needs. This guide gives coverage tables for common mast heights, the simple rules behind them, and the limits that the tables cannot show.

What sets the coverage

The lux level. Coverage is inversely proportional to it. A storage yard at 10 lux and a container handling area at 50 lux differ by five times in the area one mast can serve.

The total lumens. Number of floodlights × watts × lumens per watt.

The height. Light that leaves a floodlight close to horizontal travels far but arrives at a shallow angle. It lights the tops of objects, leaves long shadows and dazzles drivers. Height is what allows a wide throw at a steep enough angle.

Coverage tables

The lumen method links the first two:

Area = total lumens × utilisation factor × maintenance factor ÷ target lux

The tables use a utilisation factor of 0.5 (half of the light lands on the target area, a normal figure for high masts) and a maintenance factor of 0.8. Floodlights are taken at 130 lm/W, the figure for the port and apron version of our heat-pipe floodlight.

Mast Floodlights Total lumens Area at 10 lux Area at 20 lux Area at 50 lux
20 m 6 × 400 W 312,000 12,480 m² 6,240 m² 2,496 m²
25 m 8 × 500 W 520,000 20,800 m² 10,400 m² 4,160 m²
30 m 10 × 600 W 780,000 31,200 m² 15,600 m² 6,240 m²
35 m 12 × 800 W 1,248,000 49,920 m² 24,960 m² 9,984 m²

The same areas as the radius of a circle around the mast:

Mast Radius at 10 lux Radius at 20 lux Radius at 50 lux
20 m 63 m 45 m 28 m
25 m 81 m 58 m 36 m
30 m 100 m 70 m 45 m
35 m 126 m 89 m 56 m

These are averages over the area. The ground near the mast is brighter than the average and the edge is darker.

The radius-to-height rule

Divide each radius by the mast height and a pattern appears:

Light level Radius ÷ height in the tables
10 lux 3.2–3.6
20 lux 2.2–2.5
50 lux 1.4–1.6

So, with floodlights sized as above:

  • at 10 lux, one mast covers a radius of about three times its height;
  • at 20 lux, about twice its height;
  • at 50 lux, about one and a half times its height.

The rule works because experienced designers size the floodlights to the height. It also marks a limit. Beyond about three times the height, light arrives at less than 20 degrees above the ground. Adding more watts to throw light further than that gives glare and shadows, not useful coverage. If you need a wider area, raise the mast or add another one.

Why uniformity limits coverage first

Standards for outdoor workplaces set a minimum uniformity as well as an average. EN 12464-2, for example, asks for a ratio of minimum to average of 0.25 for many storage and handling areas, and 0.4 or more for demanding work.

One mast alone gives a bright centre and a fading edge. Uniformity comes from overlap: each point between masts receives light from two or more of them. That is why masts are normally spaced three to four times their height apart.

Mast height Usual spacing Area per mast in a square grid
20 m 60–80 m 3,600–6,400 m²
25 m 75–100 m 5,600–10,000 m²
30 m 90–120 m 8,100–14,400 m²
35 m 105–140 m 11,000–19,600 m²

Compare this with the first table: the grid areas sit between the 20 lux and 50 lux columns. In practice, a regular grid of masts at these spacings with the floodlight sets shown delivers roughly 20–50 lux, which is the range most yards, ports and interchanges ask for.

Shadows

The tables assume open ground. Real sites have obstructions:

  • container stacks and stored materials;
  • trucks, cranes and gantries;
  • buildings at the edge of the yard.

An object 6 m high, 60 m from a 30 m mast, casts a shadow about 15 m long. Light from one direction leaves that strip dark. The answer is light from at least two directions, which means a mast on each side of the working area or a full ring of floodlights on masts placed inside the yard.

A real configuration

At a steel pipe plant in Xiangtan we installed two 32 m masts in 2025. One carries a full ring of ten 600 W LED floodlights; the other carries a three-quarter ring of eight. Two tall masts were chosen over many short poles because poles in the yard would obstruct cranes and trucks. The three-quarter ring is the usual answer for a mast near a boundary: there is nothing to light behind it.

Choosing the beam angles

Coverage also depends on aiming. A typical mast head mixes beams:

Beam Use on a mast
25° Reaching the far edge of the area
40° Middle distances
60° General fill
90° The ground close to the mast

Our BG-TS floodlights are made in 200, 400, 500, 800, 1,000 and 1,500 W with these four beams, rated IP67. Mixing beams in one ring is what turns a bright circle into an even field.

Typical light levels by site

Site Typical average
Open storage, long-term parking 5–10 lux
Truck parks, general yards 20 lux
Container yards, loading areas 20–50 lux
Toll plazas, interchanges, apron areas 20–50 lux, by the road or airport standard
Precise work outdoors 100 lux or more, usually with local lighting

Always take the requirement from the standard or the site owner. For the airport case, see airport high mast lighting.

A quick estimate for your site

  1. Write down the area and the lux level.
  2. Lumens needed = area × lux ÷ 0.4 (that is, 0.5 × 0.8).
  3. Choose a mast height so that the furthest point is within about three times the height from a mast.
  4. Divide the lumens between the masts, and check each mast against the first table.

Example: a 200 × 120 m yard (24,000 m²) at 20 lux needs 1.2 million lumens. Two 30 m masts on the long axis, 100 m apart, each need 600,000 lumens: eight 600 W floodlights at 130 lm/W give 624,000. The furthest corner is about 78 m from a mast, 2.6 times the height, which is within the limit.

That is an estimate for budgeting. The final design should come from photometric software, with the real floodlight data. Our high mast lighting guide covers the mast, the lowering gear and the foundations, and high mast installation covers the site work.

Common mistakes

Mistake Result
Asking for “coverage” without a lux level Offers that cannot be compared
More watts on a short mast Glare and long shadows, not more coverage
One mast at the edge of a large yard Far side dim, shadows behind every stack
Narrow beams only Bright spots and dark gaps
Ignoring the maintenance factor Below target after a few years of dust

What to send for a design

A site plan with dimensions, the lux level and uniformity required, the positions where masts may stand, the height of stored goods, and the supply voltage. See our high mast lights range; we return mast positions, heights, the floodlight schedule and a lux plot.

Sources

  1. CIE 115 — Lighting of roads for motor and pedestrian traffic
  2. EN 12464-2 — Lighting of work places, Part 2: Outdoor work places
  3. BlueGreen OE — 32 m high mast lighting for a steel pipe plant, project record

Frequently asked questions

How much area does a high mast light cover?

It depends on height, total lumens and the light level required. As a guide, a 30 m mast with ten 600 W LED floodlights covers about 31,000 m² at 10 lux, 15,600 m² at 20 lux or 6,200 m² at 50 lux.

What is the coverage radius of a 30 m high mast?

About 100 m at 10 lux and about 70 m at 20 lux with ten 600 W floodlights, by the lumen method. For even light the practical radius is about two to three times the mast height, so 60–90 m.

How far apart should high masts be?

Commonly three to four times the mast height: 90–120 m for 30 m masts. Closer spacing improves uniformity and reduces shadows; wider spacing leaves dark bands between masts.

Does a taller mast cover more area?