  • Most bollard lights bolt to a small concrete footing through a base flange; the footing, anchor bolts and conduit are set before the bollard arrives.
  • Cast the anchor bolts with a template that matches the bollard's flange drawing, and bring the conduit up through the centre with a sweep bend, not a sharp elbow.
  • Sixteen of our 9 W BG-CP bollards at 5 m spacing on an 80 m path, fed from 20 m away, draw about 0.7 A at 230 V; even on 1.5 mm² cable the voltage drop is under 1%.
  • Mains bollards like the BG-CP (AC 100–240 V, IP65) need an earthed metal body, a buried cable at the depth your code requires and an RCD on the circuit.
  • Leave a drainage layer under the footing and keep the cable joint inside the bollard above any standing water.

Bollard lights are simple fittings, but they sit at ground level where water, lawnmowers, feet and sometimes vehicles all reach them. Most failures we hear about come not from the light but from the base: a footing that settled, a conduit full of water, a cable joint in a puddle. This guide covers the concrete base detail and the cabling, with a worked calculation for a typical path using our own bollards.

Plan the run before you dig

Decide the bollard positions, spacing and power first. For our LED lawn and bollard light BG-CP, 0.6 m high and 3–30 W, our published guidance is:

Effect Spacing Power
Marking a path edge 6–8 m 3–6 W
Even light along a path 4–5 m 6–9 W
Entrances and steps 2–3 m 9–18 W

Mark each position with a peg, then mark the trench line between them and back to the supply. Check for buried services before digging.

The concrete base detail

A typical footing for a 0.6–1 m bollard in firm ground:

  • Size: about 300 × 300 mm in plan, 400–500 mm deep. Increase it in soft ground, near vehicles or for taller bollards.
  • Drainage: 100 mm of compacted gravel under the concrete so water does not sit against the base.
  • Conduit: a 20–32 mm duct rising through the centre with a long sweep bend, so the cable can be pulled later. Cap it until the bollard goes on.
  • Anchor bolts: three or four galvanized or stainless bolts, set with a plywood template that matches the bollard’s base flange. Leave enough thread above the concrete for the flange, washers and nuts.
  • Top of concrete: level, finished slightly above the surrounding soil or paving so water runs away from the bollard.

Get the base-plate drawing from the supplier before casting. Bolt circle and bolt size vary between bollard designs and between makers, and a template cut to the drawing avoids drilling new holes on site.

Alternatives to a cast footing

  • Precast bases with bolts already in place save curing time on large jobs.
  • Chemical anchors into an existing slab work for bollards on paved areas, provided the slab is thick and sound.
  • Ground spikes suit only small, low-voltage garden bollards, not mains fittings.

Cable: route, depth and protection

Mains bollards such as the BG-CP run on AC 100–240 V. The rules for the supply are set by your national wiring code, often based on IEC 60364-7-714 for outdoor lighting. In general:

  • Use cable rated for direct burial (for example armoured cable) or run ordinary cable in a duct.
  • Bury it at the depth your code requires, with marker tape above it.
  • Loop from bollard to bollard, with joints made in the bollard’s terminal block or a gel-filled connector, not in the ground.
  • Protect the circuit with a breaker and a residual current device (RCD).
  • Earth the metal body of each bollard.

Voltage drop worked out for an 80 m path

A path 80 m long, lit evenly with 16 BG-CP bollards at 5 m spacing, 9 W each (about 810 lumens each at the rated 90 lm/W). The supply point is 20 m from the first bollard, so the cable is about 100 m long.

Load: 16 × 9 W = 144 W. With a power factor of 0.9 at 230 V, the current is 144 ÷ (230 × 0.9) = 0.70 A.

To be safe we put the whole load at the far end of the cable, which overstates the real drop. For copper (0.0175 Ω·mm²/m), out and back:

Cable Voltage drop Share of 230 V
1.5 mm² 2 × 100 × 0.70 × 0.0175 ÷ 1.5 = 1.6 V 0.7%
2.5 mm² 1.0 V 0.4%

Either is well within the usual 3–5% limit for lighting. With LED loads this small, cable size is chosen for mechanical strength, fault protection and the code’s minimum, not voltage drop. That changes for low-voltage 12 V or 24 V garden bollards, where the same power draws 10–20 times the current and drop becomes the main limit. Our article on low-voltage landscape lighting covers that case.

Fitting the bollard

  1. Let the concrete cure as the mix requires, usually several days before loading.
  2. Pull the cable through the conduit, leaving 300–500 mm spare inside the bollard.
  3. Fit the bollard over the bolts, level it with shims or levelling nuts, and tighten.
  4. Make the connection in the terminal block: live, neutral and earth. Keep the joint high inside the body, above any water that might collect at the base.
  5. Seal the cable entry so insects and water stay out.
  6. Test insulation and earth continuity, then energise and check each light.

Common mistakes

  • No drainage, so the base sits in water and the cable entry floods.
  • Sharp conduit elbows, which make the cable impossible to pull or replace.
  • Joints buried in the soil, which corrode within a year or two.
  • Bolts set by eye, so the bollard flange does not fit.
  • Bollards too close to the path edge, where mowers and snow ploughs hit them.

Bollards and other path lights

Bollards give a soft, low light that guides feet without glare. For long park paths, poles of 3–4 m with garden lanterns can be spaced further apart and cost less per metre; see our park lighting guide and bollard lights for comparisons, or our pole height and spacing calculator for taller options.

Send us your site plan and the effect you want; we will propose bollard spacing and wattage, and the cable and footing details to go with them.

Sources

  1. BlueGreen OE — LED lawn and bollard light BG-CP specifications
  2. IEC 60364-7-714 — Low-voltage electrical installations, external lighting installations
  3. BlueGreen OE — Pole height and spacing calculator

Frequently asked questions

How deep should a bollard light base be?

For a 0.6–1 m bollard, a concrete footing of roughly 300 × 300 mm and 400–500 mm deep is common in firm ground. Softer ground, vehicle areas and taller bollards need larger footings; follow the bollard maker's drawing and local practice.

Do bollard lights need a concrete base?

Most do. Some light bollards can be bolted to an existing slab or set on a ground spike, but a concrete footing keeps them upright and protects the cable entry.

What cable size do I need for bollard lights?

LED bollards draw little current, so voltage drop is rarely the limit. In our example, 16 × 9 W bollards on a 100 m run lose under 1% on 1.5 mm². Many installers still use 2.5 mm² armoured cable for mechanical strength.

How far apart should bollard lights be?

For 0.6 m bollards, about 4–5 m for even light along a path, 6–8 m to mark its edge and 2–3 m at entrances and steps.

Products in this guide

Have a project?

Ask our engineers

Send us your site details and we will size the system and quote it.

We reply by email within one working day (China time, GMT+8). Your details are only used to answer this inquiry. Prefer chat? Message us on WhatsApp. Have more detail to give? Use the full form.

Related guides