8 Foot T12 LED Retrofit Kits: Options, Wiring and Savings for Old Fluorescent Strip Lights
Converting 8 foot T12 fluorescent fixtures to LED: 8 ft tubes, kits with four 4 ft tubes, or new fittings. Lamp bases, ballast bypass, and a savings example.
Key points
- An 8 foot T12 fixture can be converted three ways: 8 ft LED tubes, a retrofit kit that takes four 4 ft LED tubes, or a new LED fitting.
- Check the lamp base first: single-pin slimline lamps and recessed double-contact high-output lamps use different holders, and neither accepts a 4 ft two-pin tube.
- A two-lamp 8 ft T12 fixture draws about 172 W with its magnetic ballast; four 18 W LED tubes draw 72 W, a saving of 58%.
- For 100 fixtures used 3,000 hours a year, that is about 30,150 kWh saved, or 4,520 a year at 0.15 per kWh.
- Four 18 W tubes at 90 lm/W give 6,480 lumens, all directed downward; measure the light level on one trial fixture before converting the building.
Eight foot T12 fluorescent strips lit a generation of workshops, warehouses, garages and shops. Many are still in service, with dim, flickering lamps and humming ballasts, and the lamps and ballasts have been withdrawn from production in many markets. Converting them to LED is one of the simplest lighting upgrades there is, but 8 foot fixtures have a few traps that 4 foot ones do not. This guide explains the options, the wiring, and what the change is worth.
First, identify what you have
| Lamp type | Typical marking | Base | Typical lamp power |
|---|---|---|---|
| Slimline, instant start | F96T12 | Single pin at each end | 60–75 W |
| High output (HO) | F96T12/HO | Recessed double contact | about 110 W |
| Very high output (VHO) | F96T12/VHO | Recessed double contact | about 215 W |
T12 means a tube 1.5 inches (38 mm) across. The base matters because it decides which LED tube can be fitted without changing the lamp holders. A standard 4 ft LED T8 tube has two pins at each end (G13) and fits none of these holders.
Note the number of lamps per fixture, the supply voltage, the mounting height and whether the fixture has a reflector.
Three ways to convert
| Option | What you do | Good points | Watch for |
|---|---|---|---|
| 8 ft LED tubes | Fit tubes with the same base, bypass the ballast | Fewest parts; fastest | Long tubes are costly to ship and easy to break; fewer makers |
| Retrofit kit with four 4 ft tubes | Fit new holders at the ends and centre, wire direct to mains | Uses standard 4 ft tubes; spares available everywhere | More wiring per fixture |
| New LED fitting | Take down the old strip; fit an LED batten or high bay | New housing, optics and warranty; chance to re-plan the layout | More labour; ceiling fixings may change |
For buyers who import in volume, the second option has a practical advantage. A 4 ft tube packs in a 1.25 m carton, ships and stores easily, and is the same lamp used across the rest of the building. Our LED T8 tube BG-RG is made in 600 mm and 1,200 mm lengths, at 8–18 W, 90 lm/W, with a 180° beam and an AC 100–240 V input. We do not make an 8 ft tube: two 1,200 mm tubes end to end replace each 8 ft lamp.
Wiring: bypassing the ballast
The principle is the same for every option. The old ballast is taken out of the circuit and the mains is taken to the lamp holders.
- Isolate the circuit at the board and prove it dead.
- Remove the lamps and the ballast cover.
- Cut the ballast out. Disconnect the supply wires and the lamp-holder wires from the ballast. Remove the ballast or leave it disconnected in place.
- Fit or re-use the lamp holders. For a kit with 4 ft tubes, fit the new two-pin holders at each end and at the centre of the housing.
- Wire the holders to the tube maker’s diagram. Single-ended tubes take live and neutral at one end only. Double-ended tubes take live at one end and neutral at the other. The two are not interchangeable.
- Check the holder type. Single-ended tubes need non-shunted holders at the live end. Shunted holders, which join the two contacts, cause a short circuit with a single-ended tube.
- Earth the housing, fit the tubes and restore power.
- Label the fixture “LED only, ballast bypassed” so that nobody fits a fluorescent lamp later.
Our guide on how to wire LED tube lights without a ballast shows the single-ended and double-ended circuits in detail. The work should be done by a qualified electrician; in some countries modifying a fixture also changes its certification status, so check the local rule.
How much light?
This is the step most often skipped. A new 75 W slimline T12 lamp is rated in the region of 6,000 lumens, so a two-lamp fixture starts life at around 12,000 lamp lumens. Four 18 W LED tubes at 90 lm/W give 6,480 lumens. On paper that is about half.
In practice the gap is much smaller, for three reasons:
- a fluorescent tube shines in all directions, and a bare strip sends much of its light onto the ceiling and into the housing, while an LED tube sends all of its light downward within 180°;
- old T12 lamps have usually lost a good part of their output, and magnetic ballasts under-run them in cold buildings;
- LED tubes give full output at once, in the cold as well.
Even so, do not assume. Convert one fixture, or one bay, and measure the light on the work surface with a lux meter before and after, in the dark. If the level is too low:
- choose higher-output tubes;
- add a reflector kit;
- or, in high spaces, change to high bays, which is covered below.
See our LED fluorescent tube replacement guide for lumens by tube size, and fluorescent tube colour temperature for the colour choice.
What it saves: a 100-fixture example
A two-lamp 8 ft fixture with 75 W slimline lamps draws about 150 W in lamps plus roughly 15% in the magnetic ballast: about 172.5 W. Four 18 W LED tubes draw 72 W. Our LED retrofit savings calculator gives, for 100 fixtures used 10 hours a day on 300 days a year:
| T12, two 75 W lamps | LED, four 18 W tubes | |
|---|---|---|
| Power per fixture | 172.5 W | 72 W |
| Energy per year, 100 fixtures | 51,750 kWh | 21,600 kWh |
| Energy cost at 0.15 per kWh | 7,763 | 3,240 |
| Saving | 30,150 kWh, 58%, 4,523 a year |
Open the example and enter your own hours, tariff and the prices you have been quoted to see the payback period.
High-output fixtures save more per fixture, because they start from a higher load, but they also need more LED lumens to match. Maintenance savings come on top: no more lamp and ballast changes on a platform.
When high bays are the better answer
Eight foot strips were often used in rows at 5–8 m in workshops and stores, because nothing better was affordable at the time. At those heights, a smaller number of LED high bays usually gives more light on the floor, with fewer fittings to wire and maintain.
| Mounting height | Sensible choice |
|---|---|
| Under 4 m | Tubes, battens or a retrofit kit |
| 4–6 m | Either; compare by measured light and cost |
| Above 6 m | LED high bays |
Our high bay lighting calculator gives the number of fittings for a building, and LED shop lights vs high bay lights compares the two approaches. For the general choice between kits and new fittings, see LED retrofit kits.
Choosing tubes for a kit
| Property | What to ask for |
|---|---|
| Wiring type | Ballast bypass; single-ended or double-ended, matching the kit |
| Lumens | Stated per tube, not only watts |
| Colour temperature | 4,000 K for general work; 5,000–6,000 K where a cooler, brighter look is wanted |
| Colour rendering | Ra 80 for work areas |
| Voltage range | Matches the supply; 100–240 V covers most countries, 277 V circuits need a suitable tube |
| Cover | Plastic, not glass, in food areas and where breakage matters |
| Temperature rating | Check for unheated buildings and cold stores |
Disposal
Fluorescent lamps contain mercury and must go to a recycler, not into general waste. Very old magnetic ballasts, generally those made before about 1980, may contain PCBs and need specialist disposal. Count this into the project.
Common mistakes
| Mistake | Result |
|---|---|
| Ordering 4 ft tubes without a kit for 8 ft holders | Tubes do not fit |
| Leaving the magnetic ballast in circuit | Failed tubes, wasted energy |
| Single-ended tubes in shunted holders | Short circuit at switch-on |
| No trial fixture | Light level lower than expected across the whole building |
| No “LED only” label | A fluorescent lamp fitted later onto mains-wired holders |
Ordering
Tell us the number of fixtures, lamps per fixture, the supply voltage, the mounting height and the colour temperature you want. We quote 1,200 mm tubes or integrated battens by the carton, and for buildings above 6 m we will also show the high bay alternative.
Sources
Frequently asked questions
Can I put LED tubes in an 8 foot T12 fixture?
Yes. Either fit 8 ft LED tubes with the same base as the old lamps, wired directly to the mains with the ballast removed, or fit a retrofit kit that converts the fixture to hold four 4 ft LED tubes. Both need the old ballast disconnected.
What is an 8 foot LED retrofit kit?
A set of parts that turns an 8 ft fluorescent strip into an LED fixture without taking down the housing: usually a new cover plate or brackets, lamp holders for 4 ft tubes at the ends and the middle, and the wiring. Some kits use LED strips with a driver instead of tubes.
Do I need to remove the ballast for LED tubes?
For T12 fixtures, yes in almost every case. T12 magnetic ballasts are old, wasteful and not compatible with most LED tubes. Ballast-bypass tubes are wired straight to the supply, and the ballast is disconnected or removed.
Is it better to retrofit or replace 8 foot fluorescent fixtures?
Retrofit if the housings are sound and the positions are right. Replace if the housings are rusted, the lamp holders are brittle, or the building's use has changed. In high spaces, a smaller number of LED high bays is often the better replacement.